[119] Current detection circuit of transducer is abnormal
Check if wire between DCCT and
control board wire between IPM
and compressor are correct; if
wiring direction of DCCT is normal
Check if current sensor is normal
Replace inverter PCB
Correct the wiring due to
diagram
Replace current sensor
Y
Y
N
N