131
[38,40] High pressure too high/low protection(Pd)
Replace pressure sensor
If characteristic of high pressure
sensors are normal
If stop valve opens fully
If in cooling outdoor fan motor
runs normally
If in heating indoor fan motor runs
normally and if filter is clogged
Check if piping
system is clogged
Open stop valve
Check fan motor
Check indoor
Clear the piping
N
Y
Y
Y
N
N
N
N
Y
N
If the refrigerant quantity of
the system is abnormal
Charge refrigerant according
to the standard
Y