112
0010
Outdoor temperature
R
Unit: °C Send Value = Actual value *10 int16,16 numbers with
positive and negative
0011
Reserved
R
Reserved (Default is 0)
0012
Current fault
R
Integer between 0-130, 0 means no fault
0013
Historical fault 1
R
0014
Historical fault 2
R
0015
High Pressure
R
Unit: 0.01kgf Send Value = Actual value *100,16 positive
numbers
0016
Low Pressure
R
Unit: 0.01kgf Send Value = Actual value *100,16 positive
numbers
0017
Frequency
R
Unit 0.1hz, Send Value = Actual value *10,16 positive numbers
0018
The quantity of indoor
unit’s controllers
R
0-64 (0 means none)
0019
Reserved
R
Reserved
0020~0149
Reserved
R
Reserved (The default is 0)