Table 1 – Maximum refrigerant charge allowed in a room
Aroom (m²)
Maximum refrigerant charge in a room / m
max
(kg)
H=1.15m
H=1.20m
H=1.30m
H=1.40m
H=1.50m
H=1.60m
H=1.70m
H=1.80m
1
0.265
0.276
0.299
0.322
0.345
0.368
0.391
0.414
2
0.530
0.553
0.599
0.645
0.691
0.737
0.783
0.829
3
0.794
0.829
0.898
0.967
1.036
1.105
1.174
1.243
4
1.059
1.105
1.197
1.289
1.382
1.474
1.566
1.658
5
1.324
1.382
1.497
1.612
1.727
1.842
1.957
2.072
6
1.589
1.658
1.796
1.934
2.072
2.210
2.349
2.487
7
1.738
1.814
1.965
2.116
2.267
2.418
2.570
2.721
8
1.858
1.939
2.101
2.262
2.424
2.585
2.747
2.909
9
1.971
2.057
2.228
2.399
2.571
2.742
2.914
3.085
10
2.078
2.168
2.349
2.529
2.710
2.891
3.071
3.252
11
2.179
2.274
2.463
2.653
2.842
3.032
3.221
3.411
12
2.276
2.375
2.573
2.771
2.969
3.166
3.364
3.562
• For intermediate H values, the value that corresponds to the lower H value from the table considered.
Example:
For H=1.25 m, the value that corresponds to H=1.20 m is considered.
• For intermediate B
room
values, the value that corresponds to the lower A
room
value from the table is considered.
Example:
For A
room
=10.5 m², the value that corresponds to A
room
=10 m² is considered.
VA
min
VA
min
Содержание HU062WAMNA
Страница 1: ...ATW Split Service Manual SYJS 2022 A Edition 2022 A ...
Страница 16: ...16 6 Piping Diagram ...
Страница 25: ...25 Cooling Tao C Two C Ta Ambient temperature Two Outlet water temperature ...
Страница 79: ...79 No Drawing Name of parts Quantity 1 Drainage elbow 4 2 Rubber cushion 4 Accessories ...