[111] Compressor out of control
[118] The compressor startup failure
Improve power supply circuit
Check if voltage of power
supply is normal
Check the wires among U, V, W of
compressor are normal
If compressor is normal
(compressor coil resistor,
insulation)
Compressor load
too much, check
the reason
Replace the wires
Replace the compressor
N
Y
Y
Y
N
N