109
SMG2-2 SMG1-1 SMG1-2
Function
Digital tube display
15 (F)
0
2
Pipe length selection
0: Middle pipe length;
1:Short pipe length;
2: Long pipe length.
15 (F)
1
2
Defrost in selection
0: Area hard to defrost;
1: Area easy to defrost;
15 (F)
2
2
Defrost exit selection
0: Normal defrost;
1: Strength defrost (extend the defrosting
time);
15 (F)
3
2
Start mode prior selection
0: First opened in priority;
1: Later opend in priority;
2: Cooling in priority;
3: Heating in priority
15 (F)
4
2
Power suppression operation
control mode selection (no
connection with I/O board)
0: According to E2 (no outer siginal);
1: According to outer DRM
15 (F)
5
2
Power suppression operation
control mode selection (E2
with no outer siginal) (no
connection with I/O board)
11 levels in total, level 0 is 0%, level 10 is
100%
15 (F)
6
2
Operation mode
0: heat pump;
1: cooling only;
2: heating only
15 (F)
7
2
Power suppression operation
control mode selection
(according to the limit value
of I/O board)
11 levels in total, level 0 is 0%, level 10 is
100%
15 (F)
8
2
Module low power selection
0: OFF;
1: ON
15 (F)
9
2
Modbus protocol selection
0: Outdoor control board passively respone;
1: Outdoor control board actively siginalling;
2: Knotbase EP485
3: Standard modbus protocol
15 (F)
10 (A)
2
LEV fault masking selection 0: Nromal detect fault
1: Mask fault
15 (F)
11 (B)
2
2-way valve interlock "three
no" installation mode special
control selection
0: OFF;
1: ON
15 (F)
12 (C)
2
Power limit operation control
mode selection
0- By E2 value,
1- By external contact DRM
15 (F)
13 (D)
2
Power output ratio selection
(E2 control method is valid)
Maximum capacity to allow the maximum
number of files, a total of 11 stalls, 0 stalls
for 10, 0%, 100%
15 (F)
14 (E)
2
Heating expansion valve
control
0: Normal control (Use of Two)
1: Isentropic control (Use of entropy)
Each item needs to be set, setting method as below:
(1)Press ENTER (SW7) for 3 seconds to enter the setting state, flashing display the current value.
(2)Press UP (SW4) or DOWN (SW5) to adjust parameters.
(3)After the adjustment is completed,
<A> In the current state of dip switch, press ENTER (SW7) for 3 seconds in the effective settig time, save the
current value then exit the setting state, flash will stop. Power off after 5 seconds then power on again.
<B>Without pressing ENTER (SW7) in the effective settig time, and without saving the current value and exit the
setting state, flash will stop
E2 control parameters display and setting
Содержание HU062WAMNA