Reverse osmosis system
GENO-OSMO RO 125K
Order no. 285 752 940-inter Edited by: phar-mrie G:\BA-752940-INTER_285_RO_125K.DOCX
32
Table E-1: Extract from point F-3.1 input logic code 113
Display
factory
setting
Parameters
Setting
range
Comments
E-A: 1
Contact type level "a"
0 ... 1
0 = NO contact
1 = NC contact
E-b: 0
Contact type level "b"
0 ... 1
0 = NO contact
1 = NC contact
E-c: 0
Contact type level "c"
0 ... 1
0 = NO contact
1 = NC contact
EHP: 2
Type of contact
pressure switch
negative pressure HP
(high-pressure pump).
0 ... 3
0 = NO contact
1 = NC contact
2 = NO contact with auto
restart
1)
3 = NC contact with auto
restart
1)
EPS: 0
Contact type pressure
switch PS (pressure
booster pump).
0 ... 1
0 = NO contact
1 = NC contact
ECL: 0
Contact type close
input.
0 ... 1
0 = NO contact
1 = NC contact
EnL: 0
Rinse system (inlet
and rinsing solenoid
valves).
0 ... 1
1 = Open solenoid valves
(only possible if the
system is switched
off using ▼ button).
0 = Close solenoid valves
again
A.PF:0
Function signal contact
terminals 15/17.
0 ... 1
0 = Contact opens when
HP pressure switch
is deenergised,
conductivity pre-
warning, level has
fallen below "c",
maintenance interval
expired.
1 = Contact closed when
HP pump running.