Reverse osmosis system
GENO-OSMO RO 125K
Order no.
285 752 940-inter Edited by: phar-mrie G:\BA-752940-INTER_285_RO_125K.DOCX
25
Warning!
The installation site must have a floor drain. If no floor drain
is available, an adequate safety device needs to be installed (refer to
option C-6).
Warning!
Floor drains that discharge to a lifting system do not work in
case of a power failure.
Recommendations
Install a sampling valve immediately before and after the reverse
osmosis system GENO-OSMO RO 125K. This simplifies the sampling
for the regular quality control (functional check).
1.2 Electrical
installation
Internal wiring control GENO-OSMO-RO125K
The system is completely pre-wired (possibly including options) and
delivered ready to plug in. During commissioning, parameter ECL:1
must be reprogrammed to ECL:0 at code level 113 (NC contact
>>NO contact). This is a protective measure to prevent the system
from being inadvertently switched on after the power cable has been
plugged in, without the system having been vented first.
Jumpers must be plugged in like this
C
o
nduc
tiv
ity
m
o
dul
e
Mains cable
PS-pump
(pressure booster)
HP-pump
Thermal circuit breaker
of HP-pump
Release of analysis
Hardness monitoring device
Pumps
Solenoid
valve
Mains
Fig. D-1: Printed circuit board assignment GENO-OSMO RO 125K