Reverse osmosis system
GENO-OSMO RO 125K
Order no. 285 752 940-inter Edited by: phar-mrie G:\BA-752940-INTER_285_RO_125K.DOCX
24
D
Installation
1 | General installation information
The installation site must offer adequate space. A foundation of a
sufficient size and adequate load carrying capacity has to be provided.
The required connections must be provided prior to the installation.
Dimensions and connection data are summarised in table C-1.
Note:
Also observe the operation manuals that have been supplied
with the optional accessories (see chapter C, 5.2) for your system
(if applicable).
1.1 Sanitary
installation
Certain binding rules must always be observed when installing
the reverse osmosis system GENO-OSMO RO 125K. Additional
recommendations are given in order to facilitate the handling of
the system. The installation instructions described below are also
illustrated in fig. D-4.
Mandatory regulations
The installation of a reverse osmosis system GENO-OSMO RO 125K
represents a major interference with the drinking water system.
Therefore, only authorised experts may install such systems.
Observe local installation guidelines and general regulations.
Install a drinking water filter upstream (e.g. BOXER KD) (option).
Install a system separator upstream (option).
Install a water softener upstream (option).
Install an activated carbon filter upstream, if required (option).
Provide a drain connection (minimum DN 50) to discharge the
concentrate.
Note:
If the concentrate is directed to a lifting system, the delivery
rate of the lifting system should at least be 500 l/h.