Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
74
①
For modular outdoor units, if there are multiple outdoor modules, then the master unit
must be the first outdoor module on the communication wire and should not connect
with IDU (master unit is set by S7 of the outdoor main board).
②
For modular outdoor units, if there are multiple outdoor modules, then the indoor units
must be connected with the last slave module of ODU (slave unit is set by S7 of the
outdoor main board).
③
The communication cable and power cable must be laid separately to avoid interference.
④
The communication cable must be long enough to avoid joints.
⑤
Indoor units must be connected in series. The last mode exchanger shall be connected
to a matching resistor (placed in the package of the ODU). The ODU D1/D2 must be
connected with the communication matched resistance (installed before factory)
⑥
For modular outdoor units, if there are multiple outdoor modules, the communication
matched resistance (installed before factory) of slave modules connecting with D1/D2
must be removed.
⑦
For modular outdoor units, if there are multiple outdoor modules, S7 dip switch of
master unit is
“00”, and S7 dip switch of slave unit is “10”, otherwise, the system main
board will display CJ which means address DIP switch code of system is shocking.
⑧
For multi-refrigeration systems, when it is necessary to connect with a centralized
controller, the communication lines connecting with all the ODUs G1/G2 must be
connected in series, and the last refrigeration system master unit G1/G2 must be
connected with the communication matched resistance (supplied in the list of ODU
spare parts).
⑨
For multi-refrigeration systems, the address dip switch S3 of the master unit must be set
by different numbers according to Ultra Heat technical service manual, and slave unit S3
can’t be set.
3.3.2 Communication cable connection between the IDU and wired controller
Connection modes for the communication cable between the IDU and wired controller are shown in
the following figures.
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...