Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE
178
7. Check and install the front
panels.
●Check various parts and connecting lines.
●If no problem is found, hook the front panels
and tighten the screws.
5 UNIT MAINTENANCE
Check and maintain the unit periodically can prolong the service life of the unit. Please appoint
professional person to conduct the maintenance.
5.1 ODU Heat Exchanger
ODU heat exchangers should be cleaned regularly, two months a time at least. Use an absorber
and
nylon brush to clear surface dusts and stains. If a compressed air ejector is available, spray the
heat
exchanger with the ejector to clear the dirt. Water is prohibited.
5.2 Discharge Pipe
Periodically check discharge pipes for blockage to make condensing water discharged freely.
5.3 Pre-Season Cautions
(1) Check IDU and ODUs‘ air inlets and outlets for blockage.
(2) Check whether they are properly earthed.
(3) Check batteries of the remote control.
(4) Check whether air filters have been properly installed.
(5) Turn the power switch on 8 hours beforehand to pre-heat the outdoor compressor crankcase
before the unit is restarted after being in idle status for a long time.
(6) Check ODU installation. If an abnormality is found, please contact GREE‘s maintenance center.
5.4 Post-Season Maintenance
(1) Disconnect the general power supply.
(2) Clean air filters and ODUs.
(3) Clear dusts and stains off IDUs and ODUs.
(4) For rusty ODUs, apply some paint on them to prevent deterioration.
5.5 Parts Replacement
Contact GREE‘s local office or dealers to obtain parts.
Note: In the course of air tightness and leakage test, prevent oxygen or acetylene from entering
cooling circuits.
Nitrogen or refrigerant is recommended.
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...