Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
83
Step 11: Remove the pressure gauge.
2.2 Refrigerant Perfusion During Running
Step 1: Turn off the valve of the refrigerant tank and reconnect the pressure gauge pipe. Disconnect
the low pressure gauge pipe from the detection valve opening of the gas pipe and connect it to the low
pressure check valve, as shown in the following figure.
Step 2: Turn on the valves for the liquid and gas pipes of each module completely.
Step 3: Make the system to run in commissioning mode via the commissioning software or the main
board of the ODU. (For details, see the description on commissioning.)
Step 4: When the commissioning step goes to refrigerant perfusion, turn on the valve of the
refrigerant tank and perfuse the remaining quantity.
Step 5: After all refrigerant is perfused, turn off valve of the refrigerant tank and wait till
commissioning is automatically is completed for the system.
Step 6: Remove the pressure gauge to finish refrigerant perfusion.
Because R410A is a mixture of refrigerant, therefore, it must be charged in a liquid form.
Otherwise, unit will not work stably and effectively.
Do not expose the R410A refrigerant tank to direct sunlight. Otherwise, the internal pressure may
get too high and cause explosion.
Pipeline for the R410A refrigerating system must have relevant valid certificates.
During welding, avoid overheating the pipeline.
System must not filled with refrigerant other than R410A.
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...