Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
46
Module
’s capacity C (Btu/h)
Model
C
≤
327500
ML01R
327500 < C
ML02R
5.3 Branch selection of mode exchanger (A1, A2)
Model selection for branch
―A1
、
A2
‖ of mode exchanger
R410A refrigerant system
Total Capacity of the Downstream Indoor Unit X(Btu/h)
Model
Y-Type Branch Pipe
X≤17100
FQ01Na/A
17100
<
X≤72000
FQ02Na/A
72000
<
X≤96000
FQ03Na/A
96000
<
X≤232000
FQ04Na/A
232000
<
X≤327500
FQ05Na/A
327500
<
X
FQ06Na/A
5.4 Piping size among upstream branches of mode exchanger (n1, n2, n3,
n4)
Piping requirement among upstream branches of mode exchanger (n1, n2, n3, n4)
Total rated capacity of
downsteam indoor units:
X(Btu/h)
Size of connection pipe between branches of mode exchanger
Low pressure gas pipe
mm(inch)
Liquid pipe mm(inch)
High pressure gas pipe
mm(inch)
X≤17100
Φ12.7(1/2)
Φ6.35(1/4)
Φ12.7(1/2)
17100
<
X≤48500
Φ15.9(5/8)
Φ9.52(3/8)
Φ12.7(1/2)
48500
<
X≤72000
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
72000
<
X≤96000
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
96000
<
X≤120000
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
120000
<
X≤144000
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
144000
<
X≤168000
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
168000
<
X≤216000
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
216000
<
X≤240000
Φ34.9(1-3/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
240000
<
X≤312000
Φ34.9(1-3/8)
Φ19.05(3/4)
Φ28.6(1-1/8)
312000
<
X≤336000
Φ34.9(1-3/8)
Φ19.05(3/4)
Φ28.6(1-1/8)
336000
<
X≤360000
Φ41.3(1-5/8)
Φ19.05(3/4)
Φ34.9(1-3/8)
5.5 Piping size among downstream branches of mode exchanger (a, h)
Rated capacity of indoor unit
C(Btu/h)
Pipe between branches and mode exchanger
Gas Pipe mm(inch)
Liquid Pipe mm(inch)
C≤9500
Φ9.52(3/8)
Φ6.35(1/4)
9500
<
C≤17100
Φ12.7(1/2)
Φ6.35(1/4)
17100
<
C≤48500
Φ15.9(5/8)
Φ9.52(3/8)
5.6 Branch selection of downstream indoor unit of mode exchanger (B1,
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...