Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE
145
new project number.
Method 3: If the IDU is configured with the Debugger, configure a new project number through this
software.
TIP:
If there are N units within the network, the units should be numbered from N+1.
Special situation:
In some cases, the created project number is identical to that of a unit within the network. In this
case, you can use the ―one-key IDU project number reset
‖
function. However, this function will cause
the project number of the entire system to be re-distributed; thus, original number will be changed. If you
do not expect this result, forbid the use of this function and replace the AP1 again.
Methods to use the ―one-key IDU project number reset
‖
function:
Method 1: If the IDU is configured with wired control, set P45 to reset IDU project number through
one key function.
Method 2: If the IDU is configured with lamp board, use the special control YV1L1 to set P45 and
reset IDU project number through one key function.
Method 3: On the AP1 of the master ODU, press and hold SW5 for 10 seconds at least to clear all
project numbers of the IDUs and then redistribute project numbers. Other parameters are kept
unchanged.
After replacing the main board of master indoor unit, the master indoor unit must be reset.
1.1.4 Cautions on replacement of slave IDU AP1
If the AP1 of a slave IDU needs to be replaced, after it is powered on,
―Project number conflict (C5)‖
alarm may be reported. Refer to section 2.3
―Cautions on Replacement of Master IDU AP1‖ to address
the issue.
1.2 Cautions on Wired Control Replacement
1.2.1 Cautions on wired control XK46 replacement
(1) If the wired control to be replaced controls only one IDU, directly replace the control.
(2) If the wired control to be replaced controls multiple IDUs, perform the steps below first:
Set the wired control parameter ―P14
‖
to change the number of managed IDUs to the actual
quantity the control manages. For example, if the wired control manages 3 IDUs, set this parameter to 3.
If you keep the default value 1, the LCD displays L9 (as shown in the figure below).
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...