Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION
50
①
Always careful not to leak the refrigerant during welding.
②
The refrigerant generates poisonous gas harmful to human body if combusted.
③
Do not perform welding in a closed space.
④
Be sure to close the cap of the service port to prevent gas leakage after the work.
Please block the pipe knock outs of the front and side panels after installing the pipes.(Animals or
foreign objects may be brought in to damage the cables.)
1.2 Processing to Refrigerant Pipes
1.2.1 Cut-off and burring
Use a special-purpose pipe cutter to cut copper pipes instead of using a hacksaw.
Cut the pipes gently to ensure that the copper pipe does not deform.
After cutting the pipes, use a slicker to grater bur the pipes with the pipe opening inclining downward
so that the copper scales do not fall into the pipe.
Allowable deviation: Skewness of the cross section cannot exceed 1% of the copper pipe caliber.
If the copper pipe is not used immediately after cut-off, cover it with a sealing cap or adhesive tape.
1.2.2 Pipe cleaning
Cleaning with a piece of silk cloth: wrap a thin steel wire with a piece of clean silk cloth. Crumple the
cloth into a lump with diameter larger than the pipe calibre. Apply several drops of chlorylene to the cloth.
Push the cloth in from one end of the pipe and pull out from the other end. Every time the cloth is pulled
out, remove the dust and sundries with chlorylene. Wash repeatedly until the pipe is clean. This method
applies to straight pipes.
Cleaning with nitrogen: blow off all dust and sundries in the pipe with nitrogen. This method applies
to coils.
After cleaning, cover the both ends of the pipe with a sealing cap or adhesive tape.
1.2.3 Pipe bending
Processing methods:
Manual bending: applies to thi
n copper pipes (Φ6.35 mm (1/4 inch) to Φ12.7 mm (1/2 inch))
Mechanical bending: applicable range (Φ6.35mm (1/4 inch) to Φ54.1mm (2-1/4 inch))
Requirements:
The radius of the bending pipe must exceed 3.5D. The ratio of the short diameter after bending to
the original diameter must exceed 2/3.
Precautions:
During bending, there must be no corrugation or deformation inside the pipe.
The welding point of the pipe should not be at the bending part. The distance between the nozzle
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...