CAD1
Alarm
Communication Error
Fluid Panel
The control
interface has lost
communication with
the fluid panel or FCM
cube.
• Verify the CAN connection
on the system.
See
Connect the CAN Cables, page 22
• Verify the CAN connection on the
FCM cube (412).
• The FCM has an incorrect CAN ID.
• Check the status LEDs on the
FCM cube (412).
• Cycle power off and on.
CAC1
Alarm
Communication Error
Solenoid Controller
The control
interface has lost
communication
with the solenoid
controller.
• Verify the CAN connection
on the system.
See
Connect the CAN Cables, page 22
• Verify the CAN connection on the
solenoid controller board.
• The solenoid controller board has
an incorrect CAN ID.
• Check the status LEDs on the
solenoid controller board.
• Cycle the power off and on.
CDD0
Alarm
Duplicate Fluid Panel
The system detects
multiple fluid panels
set to the same
identifier.
• The fluid panel FCM has the same
CAN ID as another module.
• Adjust the selector switch on the
control module. See Adjusting
Selector Switch in manual 3A3954.
CDC0
Alarm
Duplicate Solenoid
Controller
The system detects
multiple solenoid
controllers set to the
same identifier.
• The solenoid controller has the
same CAN ID as another module.
• Adjust the selector switches on the
solenoid controller board.
CAO1
Alarm
Communication Error
Logic Controller
The system has lost
communication with
the control interface.
• Verify the CAN connection on the
bottom of the control interface.
• Check the status LEDs on the con-
trol interface. See
.