Password
If the password is not “0000”, the password must be
entered to access the setup screens.
System 1
External Pump Control: Enable feature that
automatically turns on and off the pump when using
a handheld dispense gun with an integrated trigger
switch.
Enable Diagnostic Screen: Choose whether to show
the Diagnostic screen.
Enable Temp. Adjustments: Allows temperature
adjustments on the Heat-A and Heat-B Run screens.
Enable Pump Autostart: Automatically turns the
pump on after reaching setpoint temperature and
heat soak is complete.
Enable Tandem System: Enable all secondary
system ADM screens.
Heat Soak: Time for to preheat after all zones have
reached their target temperatures. Pump cannot
turn on until timer is complete. The heat soak is a
user-defined time.
• Range: 0–120 minutes
• 0 disables heat soak
Pump Inactive Timeout: If no pump movement is
detected or either pump for (x) amount of time, all
heated zones enter setback mode. After an additional
amount of time (x), the heat will turn off.
• (x) Range: 0–120 minutes
• 0 disables heat soak
System 2
Enter low and high temperatures for an alarm or
warning to occur.