14

On/Off Switch

Inlet

Pressure Boss

High Fire

Coil Terminal (HI)

Low Fire

Regulator Adjust

Manometer

Manometer

Hose

A

High Fire Regulator

Adjust

Regulator

Vent

Common

Terminal (C)

Coaxial Coil

Terminal (M)

Outlet

Pressure Boss

Open to

Atmosphere

White-Rodgers Model 36G54 connected to Manometer

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accor-

dance to the type of fuel being consumed.

With Power And Gas Off:

NOTE

: Use adapter kit #0151K00000S to measure gas pres-

sure on White-Rodgers 36G54 gas valves.

1. 

Back inlet pressure test screw (inlet pressure boss) out 

one turn (counterclockwise, not more than one turn). Al

-

ternately, inlet gas pressure may be measured by remov-

ing the cap from the drip leg and installing a predrilled cap 

with a hose barb fitting.

2.  Connect a water manometer or adequate gauge to the 

inlet pressure tap of the gas valve (or hose barb fitting on 

predrilled cap).

With Power And Gas On:

3.  Put unit into heating cycle and turn on all other gas con-

suming appliances.

Natural

Min. 5.0" W.C., Max. 10.0" W.C.

Propane

Min. 11.0" W.C., Max. 13.0" W.C.

INLET GAS PRESSURE

Inlet Gas Pressure Must be within the Minimum and Maximum Value 

Shown in Table Above. 

NOTE: 

 Inlet Gas Pressure must be within the minimum and 

not exceed the maximum value shown. If operating pressures 

differ from above, make necessary pressure regulator adjust

-

ments, check piping size, etc., and/or consult with local utility.

4. 

Turn off all electrical power and gas supply to the system.

5.  Remove manometer hose from the outlet pressure 

boss (or remove hose from hose barb).

6.  Turn inlet pressure test screw in to seal pressure port 

(clockwise, 7 in-lb minimum). Alternately, remove pre

-

drilled cap from drip leg. Reinstall original cap, sealing 

with pipe thread compound.

7.  Turn on electrical power and gas supply to the system.

8.  Turn on system power and energize valve.

9.  Using a leak detection solution or soap suds, check for 

leaks at the pressure boss screw (or drip leg cap). Bub

-

bles forming indicate a leak. SHUT OFF GAS AND FIX 

ALL LEAKS IMMEDIATELY.



.

Measuring Inlet Gas Pressure  Alternate Method

Manifold Pressure Check 

1. 

Turn  OFF  gas  to  furnace  at  the  manual  gas  shutoff 

valve external to the furnace.

2. 

Turn off all electrical power to the system.

3. 

Back outlet pressure test screw (outlet pressure boss) 

out one turn (counterclockwise, not more than one turn).

4.  Attach a hose and manometer to the outlet pressure 

boss of the valve.

5.  Turn ON the gas supply.

6. 

Turn on power and energize main (M) solenoid. Do not 

energize the HI solenoid.

7. 

Measure gas manifold pressure with burners firing. Ad

-

just manifold pressure using the Manifold Gas Pres-

sure table.

8. 

Remove regulator cover screw from the low (LO) outlet 

pressure regulator adjust tower and turn screw clock-

wise to increase pressure, or counterclockwise to de-

crease pressure.

9. 

Energize main (M) solenoid as well as the HI terminal.

10. Remove regulator cover screw from the HI outlet pres-

sure regulator adjust tower and turn screw clockwise 

to increase pressure, or counterclockwise to decrease 

pressure.

11. 

Turn off all electrical power and gas supply to the system.

12. Remove manometer hose from outlet pressure boss.

13. Turn outlet pressure test screw in to seal pressure port 

(clockwise, 7 in-lb minimum).

14. Turn on electrical power and gas supply to the system.

15. Turn on system power and energize valve.

16. Using a leak detection solution or soap suds, check 

for leaks at pressure boss screw. Bubbles forming in-

dicate a leak. SHUT OFF GAS AND FIX ALL LEAKS 

IMMEDIATELY.

Содержание GPG 16 M Series

Страница 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Страница 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Страница 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Страница 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Страница 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Страница 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Страница 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Страница 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Страница 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Страница 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Страница 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Страница 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Страница 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Страница 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Страница 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Страница 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Страница 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Страница 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Страница 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Страница 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Страница 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Страница 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Страница 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Страница 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Страница 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Страница 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Страница 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Страница 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Отзывы: