background image

16

4.  Consult proper table for quantity of air.

If the external static pressure exceeds the minimum or max-

imum allowable statics, check for closed dampers, dirty fil

-

ters, undersized or poorly laid out ductwork.

Blower Speed Adjustments

Blower speeds are changed at the indoor blower. The igni-

tion control board has four blower speeds: LOW HEAT, HI 

HEAT, LOW COOL and HIGH COOL.

EEM Blower Speed

NOTE: 

FAN ONLY energizes at LOW HEAT speed. The 

GPG16 models are equipped with EEM motors. EEM mo-

tors are constant torque motors with very low power con-

sumption. This motor is energized by 24 VAC. Adjust the 

CFM for the unit by changing the 24 VAC leads to the speed 

terminal block on the motor.

NOTE:

 Heating airflow must be adjusted to provide the tem

-

perature rise shown on rating plate. Blower speeds are pro-

grammed to deliver adequate airflow at rated external static 

pressure (ESP). Refer to airflow table provided in the Ap

-

pendix for details.

WARNING

T

AV

O

I

P

ERSON

A

I

NJURY OR DE

A

TH  DUE TO ELECTR

I

C  SHOCK, REMO

V

E

ELECTR

I

C

A

P

O

W

ER FROM THE  UN

I

T BEFORE CH

A

N

GI

N

G

 S

P

EED T

AP

S  ON THE

BLO

W

ER  MOTOR.

Limit Check

 

Check limit control operation after 15 minutes of operation 

by blocking the return air grille(s).

1.  After several minutes the main burners must go OFF. 

Blower will continue to run.

2.  Remove air restrictions and main burners will relight 

after a cool down period of a few minutes.

Adjust the thermostat setting below room temperature.

1.  Main burners must go OFF.

2.  Circulating Air Blower will continue to run for 90, 120, 

150 or 180 seconds, depending on the setting.

NOTE:

  If necessary, adjust fan OFF delay settings to obtain 

satisfactory comfort level.

Control Board (Top)

Unit Shutdown

1.  Set the thermostat to lowest setting.

2. 

Turn off the electrical power supply to the unit.

3.  Remove the heat exchanger door on the side of the 

unit by removing screws.

4.  Move the gas control valve switch to the OFF position.  

Do not force.

5. 

Close manual gas shutoff valve external to the unit.

6.  Replace the heat exchanger door on the unit.

7.  If cooling and/or air circulation will be  desired, turn ON 

the electrical power.

Cooling Startup

NOTE:

 The outdoor temperature must be 60°F or higher be-

fore making adjustments to charge.

Compressor Protection Devices

The compressor includes components which are designed 

to protect the compressor against abnormal operating con-

ditions.

Cooling Refrigerant Charging 

Check unit charge before putting the cooling section into full 

operation. The unit has a thermostatic expansion valve me-

tering device. To ensure the unit is properly charged for the 

intended application, check the unit refrigerant sub-cooling 

at the condenser. The refrigerant sub-cooling is a function of 

outdoor ambient temperature and return air temperature of 

the conditioned space. It is the installing contractors respon-

sibility to ensure the proper refrigerant sub-cooling at the 

condenser is adjusted for each application. As the outdoor 

ambient temperature rises the sub-cooling decreases and 

as the outdoor ambient temperature lowers, the sub-cooling 

increases. 

NOTE:

 Proper sub-cooling adjustment optimiz-

es cooling performance. Models equipped with thermostatic 

Содержание GPG 16 M Series

Страница 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Страница 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Страница 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Страница 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Страница 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Страница 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Страница 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Страница 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Страница 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Страница 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Страница 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Страница 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Страница 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Страница 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Страница 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Страница 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Страница 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Страница 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Страница 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Страница 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Страница 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Страница 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Страница 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Страница 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Страница 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Страница 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Страница 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Страница 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Отзывы: