Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at
11" W.C. Setting. Capacities in 1,000 BTU/HR
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
1"
1-1/4"
1-1/2"
10
49
110
206
348
539
291
608
1,146
2,353
3,525
20
34
76
141
239
368
200
418
788
1,617
2,423
30
27
61
114
192
296
161
336
632
1,299
1,946
40
23
52
97
164
253
137
284
541
1,111
1,665
50
20
46
86
146
224
122
255
480
985
1,476
60
19
42
78
132
203
110
231
436
892
1,337
80
16
36
67
113
174
94
198
372
764
1,144
100
14
32
59
100
154
84
175
330
677
1,014
125
12
28
52
89
137
74
155
292
600
899
150
11
26
48
80
124
67
141
265
544
815
200
10
22
41
69
106
58
120
227
465
697
250
9
19
36
61
94
51
107
201
412
618
300
8
18
33
55
85
46
97
182
374
560
350
7
16
30
51
78
43
89
167
344
515
400
7
15
28
47
73
40
83
156
320
479
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
NOMINAL PIPE SIZE,
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
PIPE OR
TUBING
LENGTH,
FEET
ELECTRICAL WIRING
Thermostat Location
Mount the thermostat approximately five feet above the
floor, in an area that has an inside, vibration-free wall and
has good air circulation.
Movement of air must not be obstructed by furniture, door,
draperies, etc. The thermostat must not be mounted where
it will be affected by drafts, hot or cold water pipes or air
ducts in walls, radiant heat from fireplace, lamps, the sun,
television, etc. Consult the Instruction Sheet packaged with
thermostat for mounting instructions.
All units have two stages of heating and two stages of me-
chanical cooling. Units which will have economizers may
use thermostats with two or three stages of cooling. All units
can use single stage or multi-stage thermostats. Refer to
figures later in this section for wiring.
The units are designed for operation on 60 hertz current and
at voltages as shown on the rating plate. All internal wiring
in the unit is complete. It is necessary to bring in the power
supply to the contactor as shown on the unit wiring diagram
which is supplied with each unit. The low voltage wiring must
be connected between the unit control panel and the room
thermostat.
Single Stage Thermostat
To use a single stage thermostat, move jumper located to the
left of the terminal strip labeled “Stage Delay” from NONE to
“5” or “10” minutes. This selection will cause the control to
run on low stage for the selected time (5 or 10 minutes) then
shift to HIGH STAGE. This option controls both cooling and
heating modes. If the jumper is not moved, only low-stage
cool and low-stage heat will operate.
Refer to the unit wiring diagram for electrical connections.
When installed, the unit must be electrically grounded in ac-
cordance with local codes or in the absence of local codes,
with the National Electrical Code, ANSI/NFPA No. 70, and/
or the CSA C22.1 Electrical Code. Ensure low voltage con-
nections are waterproof.
R C W1W2 G Y1 Y2
R
Y2
C
Y1
W1
G
W2
I
ntegrated
Control Module
Thermostat
Two-Stage Heating
with
Two-Stage Cooling
Two-Stage Heating with Two-Stage Cooling Thermostat Diagram
5 MINUTE DELAY
PERIOD WITH
JUMPER IN THIS
POSITION
10 MINUTE DELAY
PERIOD WITH
JUMPER IN THIS
POSITION
Two-Stage Heating(timed) and Two-Stage Cooling(timed) with Single
Stage Thermostat Diagram