background image

27

Replace or Clean Filter

IMPORTANT NOTE: 

Never operate unit without a filter installed 

as dust and lint will build up on internal parts resulting in loss of 

efficiency, equipment damage and possible fire. 

A return air filter is not supplied with this unit; however, there 

must be a means of filtering the return air. An indoor air filter 

must be used with your comfort system. A properly maintained 

filter will keep the indoor coil of your comfort system clean. A 

dirty coil could cause poor operation and/or severe equipment 

damage.

The installer of your unit can tell you where your filter(s) are and 

how to clean or replace them.

Check  your  return  filter(s)  at  least  once  every  two  months. 

When they are dirty, replace or clean as required. Disposable 

type  filters  should  be  replaced.  Reusable  type  filters  may  be 

cleaned.

NOTE: 

 Reusable type filters should be washed with warm wa

-

ter, dried completely and sprayed with an adhesive according 

to the manufacturers recommendations.      

                           

You  may  want  to  ask  your  dealer  about  high  efficiency  fil

-

ters. High efficiency filters are available in both electronic and 

non-electronic types. These filters can do a better job of catch

-

ing small airborne particles.

Improper filter maintenance is the most common cause of in

-

adequate heating or cooling performance. Filters should be 

cleaned (permanent) or replaced (disposable) every two months 

or as required.  When replacing a filter, it must be replaced with 

a filter of the same type and size and always make certain the 

air flow arrows on the filter point in the proper direction.

Condenser, Evaporator and Induced Draft Motors

The bearings on the air circulating blower motor, condenser 

motor and the combustion fan motor are permanently lubricat-

ed and  require no further lubrication.

Compressor

The compressor motor is hermetically sealed and does not re-

quire additional oiling.

Aluminum  Indoor  Coil  Cleaning  (Qualified  Servicer 

Only)

This unit is equipped with an aluminum tube evaporator coil. 

The safest way to clean the evaporator coil is to simply flush the 

coil with water. This cleaning practice remains as the recom-

mended cleaning method for both copper tube and aluminum 

tube residential cooling coils. An alternate cleaning method is 

to use one of the products listed in the technical publication 

TP-109 (shipped in the literature bag with the unit) to clean the 

coils. The cleaners listed are the only agents deemed safe and 

approved for use to clean round tube aluminum coils. TP-109 is 

available on the web site in Partner Link > Service Toolkit.

NOTE:

 Ensure coils are rinsed well after use of any chemical 

cleaners.

Annual Inspection (Qualified Servicer Only)

Your package unit should be inspected by a qualified installer, 

or service agency at least twice every year. This check should 

be performed before the heating and cooling seasons begin. 

This will ensure that adequate combustion air is being drawn 

and the vent system is working properly. Particular attention 

should be paid to the following items. Repair as necessary.

•  Check physical support of the unit. Ensure it is sound 

without any sagging, cracks, or gaps, around the base.

•  Check for obvious signs of deterioration of the unit.

•  Flue Hood and Combustion Air Inlet. Check for blockage 

(wasp nest, etc.) and corrosion.

Flue Hood (Qualified Servicer Only)

•  Return Air Connection. Check for physical soundness and 

ensure that the connection is firmly sealed to the package 

unit casing.

•  Heat exchanger. Check for corrosion and/or obstructions 

within the heat exchanger passageways.

• 

Burners.  Check  for  proper  ignition,  burner  flame,  and 

flame sense.

•  Wiring. Check wires for damage. Check electrical connec-

tions for tightness and/or corrosion.

• 

Filters.  Check  that  filters  are  clean  and  in  the  proper 

placement in the unit or duct system.

•  Louvers. Inspect air inlet louvers inside the heat exchang-

er compartments. Ensure the area is clean and free of dirt 

and debris.

Clean Outside Coil (Qualified Servicer Only)

The outdoor coil should be inspected annually. It is important to 

keep the outdoor coil clean. Dirt, leaves, or debris could restrict 

the airflow. If cleaning of the outdoor coil becomes necessary, 

hire  a  qualified  servicer.  Inexperienced  people  could  easily 

puncture the tubing in the coil. 

 

Before Calling Your Servicer

• 

Check the thermostat to confirm that it is properly set.

• 

Check the disconnect switch near the unit to confirm that 

it is closed.

•  Check the electrical panel  for tripped circuit breakers or 

failed fuses. Reset the circuit breakers or replace fuses 

as necessary. 

•  Check for blockage of the indoor air inlets and outlets. 

Confirm that they are open and have not been blocked by 

objects (rugs, curtains or furniture).

• 

Check for obstructions on the unit. Confirm that it has not 

been covered on the sides or the top. Remove any ob-

struction that can be safely  removed. If the unit is covered 

with dirt or debris, call a qualified servicer to clean it. 

• 

Check the filter. If it is dirty, clean or replace it.

PACKAGE UNITS

   

- DUAL FUEL  & GAS   

                                                                                                                        

HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed by a 

qualified service agency

 before the heating and cooling seasons begin.

Содержание GPG 16 M Series

Страница 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Страница 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Страница 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Страница 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Страница 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Страница 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Страница 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Страница 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Страница 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Страница 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Страница 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Страница 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Страница 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Страница 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Страница 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Страница 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Страница 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Страница 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Страница 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Страница 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Страница 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Страница 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Страница 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Страница 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Страница 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Страница 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Страница 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Страница 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Отзывы: