background image

15

Range

Nominal

Low Stage

1.7 - 2.3" w.c.

2.0" w.c.

High Stage

3.2 - 3.8" w.c.

3.5" w.c.

Low Stage

5.7 - 6.3" w.c.

6.0" w.c.

High Stage

9.7 - 10.3" w.c. 10.0" w.c.

Gas

Manifold Gas Pressure

Natural

Propane

Manifold Gas Pressure

NOTE:

 For Natural gas to LP gas conversion, Conversion 

Kit “LPM-08” must be used. Consult your dealer for appro-

priate conversion kit(s).

Gas BTU Input Check (Natural Gas Only)

To measure the gas input use a gas meter and proceed as 

follows:

1. 

Turn off gas supply to all other appliances except the 

unit.

2.  With the unit operating, time the smallest dial on the 

meter for one complete revolution. If this is a 2 cubic 

foot dial, divide the seconds by 2; if it is a 1 cubic foot 

dial, use the seconds as is. This gives the seconds per 

cubic foot of gas being delivered to the unit.

3.  INPUT = GAS HTG VALUE x 3600 / SEC. PER CUBIC 

FOOT

Example:

  Natural gas with a heating value of 1000 BTU per 

cubic foot and 36 seconds per cubic foot as determined by 

Step 2, then: 

 

Input = 1000 x 3600 / 36 = 100,000 BTU per Hour.

NOTE: 

BTU content of the gas should be obtained from the 

gas supplier. This measured input must not be greater than 

shown on the unit rating plate.

4. 

Relight all other appliances turned off in step 1. Be sure 

all pilot burners are operating.

Main Burner Flame Check 

Flames should be stable, soft and blue (dust may cause or

-

ange tips but they must not be yellow) and extending directly 

outward from the burner without curling, floating or lifting off.

Temperature Rise Check 

Check the temperature rise through the unit by placing ther-

mometers in supply and return air registers as close to the 

unit as possible. Thermometers must not be able to sample 

temperature directly from the unit heat exchangers, or false 

readings could be obtained.

1.  All registers must be open; all duct dampers must be in 

their final (fully or partially open) position and the unit 

operated for 15 minutes before taking readings.

2.  The temperature rise must be within the range speci-

fied on the rating plate.

NOTE:

  Air temperature rise is the temperature difference 

between supply and return air.

Checking Temperature Rise

With a properly designed system, the proper amount of tem-

perature rise will normally be obtained when the unit is op-

erated at rated input with the recommended blower speed.

If the correct amount of temperature rise is not obtained, 

it may be necessary to change the blower speed. A higher 

blower speed will lower the temperature rise. A slower blow-

er speed will increase the temperature rise.

NOTE:

 Blower speed MUST be set to give the correct air tem-

perature rise through the unit as marked on the rating plate. 

External Static Pressure Check 

The total external static pressure must be checked on this 

unit to determine if the airflow is proper.

Total External Static Testing

1.  Using a digital manometer measure the static pres-

sure of the return duct at the inlet of the unit (Negative 

Pressure).

Total External Static

2. 

Measure the static pressure of the supply duct (Posi

-

tive Measure).

3.  Add the two readings together.

NOTE:

 Both readings may be taken simultaneously and 

read directly on the manometer if so desired. 

Содержание GPG 16 M Series

Страница 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Страница 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Страница 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Страница 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Страница 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Страница 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Страница 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Страница 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Страница 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Страница 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Страница 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Страница 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Страница 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Страница 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Страница 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Страница 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Страница 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Страница 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Страница 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Страница 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Страница 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Страница 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Страница 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Страница 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Страница 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Страница 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Страница 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Страница 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Отзывы: