background image

19

Low Flame Signal

Under some conditions, the fuel or air supply can create a 

nearly  invisible  coating  on  the  flame  sensor.  This  coating 

acts as an insulator causing a drop in the flame signal. If the 

flame signal drops below a predetermined value, the ignition 

control will display an error code of (1) flash on the amber 

diagnostic LED. The unit will continue to operate until the 

control can no longer detect flame.

Abnormal Operation - Cooling

Short Cycle Compressor Delay

The automatic ignition control has a built-in feature that pre-

vents damage to the compressor in short cycling situations. 

In the event of intermittent power losses or intermittent ther-

mostat operation, the ignition control will delay output to the 

compressor contactor for three minutes from the time power 

is restored or thermostat call for cooling is restored. (Com

-

pressor is off a total of three minutes). The diagnostic red 

LED will flash six (6) times to indicate the compressor con

-

tactor output is being delayed.

NOTE:

 Some electronic thermostats also have a built-in 

compressor short cycle timer that may be longer than the 

three minute delay given above. If you are using an elec-

tronic thermostat and the compressor has not started after 

three minutes, wait an additional five minutes to allow the 

thermostat to complete its short cycle delay time.

High Pressure Switch/Loss of Charge Switch

Some models include a high pressure cutout switch and/

or a loss of charge cutout switch. The high pressure cutout 

switch protects the refrigeration system from excessive op-

erating pressures. The loss of charge cutout switch protects 

the refrigeration system from very low operating pressures 

due to a loss of refrigerant. Compressor operation will be 

disabled if either of these devices opens. If either devices 

opens, the diagnostic red LED will flash (9) times to indicate 

that a refrigeration system pressure switch is open.

MAINTENANCE

Have the gas heating section of the unit checked at least 

once a year before the heating season begins, to be sure 

that the combustion air inlet and flue outlet hoods are not 

blocked by debris, which would prevent adequate combus-

tion air and a properly operating vent system.

Filter Replacement or Cleaning 

A return air filter is not supplied with this unit; however, there 

must be a means of filtering all of the return air. The filter(s) 

may be located in the return air duct(s), or return air filter 

grille(s). Consult with your installing dealer for the actual lo

-

cation of the return air filter(s) for your unit.

Dirty filters are the most common cause of inadequate heat

-

ing or cooling performance. Filter inspection should be made 

at least every two months; more often if necessary because 

of local conditions and usage.

Dirty  throwaway  filters  should  be  discarded  and  replaced 

with  a  new,  clean  filter.  Dirty  permanent  filters  should  be 

washed with water, thoroughly dried and sprayed with a filter 

adhesive before being reinstalled. (Filter adhesives may be 

found at many hardware stores.) Permanent filters should 

last several years. However, should one become torn or un-

cleanable, it should be replaced.

Cabinet Finish Maintenance

Use  a  fine  grade  automotive  wax  on  the  cabinet  finish  to 

maintain  the  finish’s  original  high  luster. This  is  especially 

important in installations with extended periods of direct 

sunlight.

Clean Outside Coil (Qualified Servicer Only)

The coil with the outside air flowing over it should be inspect

-

ed annually and cleaned as frequently as necessary to keep 

the finned areas free of lint, hair and debris.

Condenser, Evaporator, and  Induced Draft Motors 

Bearings on the air circulating blower motor, condenser mo-

tor and the combustion fan motor are permanently lubricat-

ed. No additional oiling is required.

Flame Sensor (Qualified Servicer Only)

A drop in the flame current can be caused by a nearly invisi

-

ble coating on the flame sensor. This coating, created by the 

fuel or combustion air supply, can be removed by carefully 

cleaning the flame sensor with steel wool.

Flame

Sensor

NOTE: 

After cleaning, the microamp signal should be stable 

and in the range of 4 - 6 microamps DC.

Содержание GPG 16 M Series

Страница 1: ...e and air flow may reduce energy efficiency and shorten equipment life ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MAN...

Страница 2: ...Primary Limit 18 Flame Detected with Gas Valve Closed 18 Low Flame Signal 19 Abnormal Operation Cooling 19 Short Cycle Compressor Delay 19 High Pressure Switch Loss of Charge Switch 19 MAINTENANCE 19...

Страница 3: ...RNINGS EXACTLY COULD RESULT IN SERIOUS INJURY DEATH OR PROPERTY DAMAGE NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...dition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 and National Standard of Canada CAN CSA B149 Installation Codes The heating and cooling capacities of the unit should be greater than or equal...

Страница 6: ...e for fire protection proper operation and service access see appendix These clearances must be permanently maintained The combustion air inlet and flue outlet hoods on the unit must never be obstruct...

Страница 7: ...at the altitudes shown on the rating plate The rating plate is stamped with the model number type of gas and gas input rating Make sure the unit is equipped to operate on the type of gas available Con...

Страница 8: ...drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long 5 Use two pipe wrenches when making connection to the gas valve to keep it from...

Страница 9: ...peration Because of the danger of ex plosion or fire never use a match or open flame to test for leaks Never exceed specified pressure for testing Higher pressure may damage gas valve and cause overfi...

Страница 10: ...nd two stages of me chanical cooling Units which will have economizers may use thermostats with two or three stages of cooling All units can use single stage or multi stage thermostats Refer to figure...

Страница 11: ...esidential or Manual Q Commercial All ductwork exposed to the outdoors must include a weather proof barrier and adequate insulation A duct system should be installed in accordance with Stan dards of t...

Страница 12: ...elay time expires the control will transition from low stage to high stage 6 The 30 second HEAT FAN ON delay time begins after the main burners light 7 The unit delivers heat to the conditioned space...

Страница 13: ...ated temperatures at the control are normally caused by blower failure The reason for the opening should be determined and repaired prior to resetting If the power to the unit is interrupted during th...

Страница 14: ...ternately remove pre drilled cap from drip leg Reinstall original cap sealing with pipe thread compound 7 Turn on electrical power and gas supply to the system 8 Turn on system power and energize valv...

Страница 15: ...e Rise Check Check the temperature rise through the unit by placing ther mometers in supply and return air registers as close to the unit as possible Thermometers must not be able to sample temperatur...

Страница 16: ...lower will continue to run for 90 120 150 or 180 seconds depending on the setting NOTE If necessary adjust fan OFF delay settings to obtain satisfactory comfort level Control Board Top Unit Shutdown 1...

Страница 17: ...3 Record the gauge pressure and the temperature of the line 4 The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling Subcooling Formula Sat...

Страница 18: ...d heat exchanger a failed induced draft blower or insufficient combustion air The rollout protection device is a manual reset limit located on the burner bracket The cause of the flame rollout must be...

Страница 19: ...ecked at least once a year before the heating season begins to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris which would prevent adequate combus tion air and a...

Страница 20: ...r lifting off At least once a year prior to or during the heating season make a visual check of the burner flames NOTE This will involve removing and reinstalling the heat exchanger door on the unit w...

Страница 21: ...Switch Compressor Igniter Condenser Coil Ignition Control Condenser Fan Blade Induced Draft Blower Condenser Fan Motor Pressure Switch Contactor Pressure Switch Hose Gas Manifold Thermostatic Expansio...

Страница 22: ...Flashes Indoor Outdoor Thermostat Open Cooling Only Devices Not present On All Models 9 Flashes High Pressure Loss of Charge Switch Open Cooling Only Devices Not Present On All Models Amber Light Sig...

Страница 23: ...e Height W D A B GPG1624 M41 47 51 32 34 1 2 Medium GPG1630 M41 47 51 32 34 1 2 Medium GPG1636 M41 47 51 40 42 1 2 Large GPG1642 M41 47 51 40 42 1 2 Large GPG1648 M41 47 51 40 42 1 2 Large GPG1660 M41...

Страница 24: ...ECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH C CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED CHE...

Страница 25: ...nufacturer s instal lation instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d instal lation du fabricant MINIMUM CLEARANCES UNI...

Страница 26: ...SPEED T5 COOLING SPEED GPG1642100M41 Rise Range 35 65 E S P T1 LOW STAGE HEATING SPEED T2 HIGH STAGE HEATING SPEED T3 LOW STAGE COOLING SPEED T4 HIGH STAGE COOLING SPEED T5 COOLING SPEED GPG1648100M41...

Страница 27: ...available on the web site in Partner Link Service Toolkit NOTE Ensure coils are rinsed well after use of any chemical cleaners Annual Inspection Qualified Servicer Only Your package unit should be ins...

Страница 28: ...ignment per installa on instructions Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure i s no n contact with refrigerant piping or sharp metal edges Check...

Страница 29: ...or Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Sta c Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Ci...

Страница 30: ...30 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 31: ...31 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...or Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registration You can also scan the QR code on the right for the product brand you purchased t...

Отзывы: