TS4000H
86
Specification
Description
General Purpose Installations
Maximum distance between the TS4000H and the power source @
24 VDC nominal is 3,430 feet (1040 meters)
Input Power
20 to 36 VDC range; +24 VDC nominal 0.120 A
Relay Ratings
(Optional)
8A @ 250 VAC/ 8A @ 30 VDC resistive maximum
(3x) SPDT – Warning, Alarm and Fault
Power Consumption
Start-up 125 mA, Normal Operation 120 mA
Output Current
500
Ω
maximum @ 24 VDC
Non-HART or HART not Enabled:
- Signal Range: 0-22 mA - Detection Range: 4-20 mA
- Start-up: 1.5 mA - Calibration: 1.5 mA
- Gas check: 1.5 mA - Setup mode: 1.5 mA
- Fault: < 1.0 mA - Over-range: 21.7 mA
HART:
- Signal Range:3.5-22 mA - Detection Range: 4-20 mA
- Start-up: 3.5 mA - Calibration: 3.5 mA
- Gas check: 3.5 mA - Setup mode: 3.5 mA
- Fault: 3.5 mA - Over-range: 21.7 mA
HART modified AO:
- Signal Range:1.25-22 mA - Detection Range: 4-20 mA
- Start-up: 1.5 mA - Calibration: 1.5 mA
- Gas check: 1.5 mA - Setup mode: 1.5 mA
- Fault: 1.25 mA - Over-range: 21.7 mA
Approvals Classification
Base Unit:
CSA: Class I, Division 1 & 2, Groups B, C and D;
Class II, Division 1 & 2, Groups E, F & G; Class III; Type 4X
ATEX/IECEx: II 2 G D Ex db IIB + H
2
T5 Gb, Ex tb IIIC T100°C Db
(-40°C
≤
Ta
≤
+70°C)
Interface Module:
CSA: Ex d ia IIB + H
2
T5
ATEX/IECEx: II 2 G Ex db mb ib IIC Gb (-40°C
≤
Ta
≤
+75°C)
EMC Protection
EN 50081-2, EN 50270
Status Indicator
LED Display with Normal, Gas Present, Fault and Calibration Cues
Table 43: Electrical Specifications