2
TS4000H
1.0 Before Installation
1.1 System Integrity Verification
General Monitors’ mission is to benefit society by providing safety solutions through industry-
leading products, services, and systems that save lives and protect capital resources from the
dangers of hazardous flames, gases, and vapors.
General Monitors’ safety products should be handled carefully and installed, calibrated, and
maintained in accordance with the individual product instruction manuals. To ensure operation
at optimum performance, General Monitors recommends that prescribed maintenance
procedures be followed.
1.2 Commissioning Safety Systems
Before power-up, verify wiring, terminal connections, and stability of the mountings for all
essential safety equipment including, but not limited to:
Power supplies
Control modules
Field detection devices
Signaling / output devices
Accessories connected to field and signaling devices
After the initial power-up and any factory specified warm-up period of the safety system, verify
that all signal outputs, to and from the devices and modules, are within the manufacturer’s
specifications. Initial calibration, calibration checking, and testing should be performed
according to the manufacturers’ recommendations and instructions. Proper system operation
should be verified by performing a full, functional test of all component devices of the safety
system, ensuring that the proper alarm levels occur.
Fault / Malfunction circuit operations should be verified.
1.3 Notes and Warnings
WARNING:
The TS4000H detects many extremely toxic gases. Exposure to such gases may
result in sickness or death.
WARNING:
The TS4000H contains components that can be damaged by static electricity. In
order to avoid static electricity, special care must be taken when wiring the
system to ensure that only the connection points are touched.
WARNING:
The TS4000H Base Unit is rated Explosion Proof (XP) and the Interface Module
Intrinsically Safe (IS) for use in hazardous locations.