TS4000H
23
3. To make ground connections to GM devices, refer to the following table:
From
To
TS4000H TA502A
TB1-8
COM (0 VDC)
Rear Pin
30d or 30z
Table 6: TS4000H to GM Display Device DC Ground Connections
3.5.4 Connecting Control Room Devices to the TB1 Block
The TB1 terminal block supports the connection from the TS4000H Base Unit to a power
supply. It also has several types of output signal connections that can be forwarded to readout
modules, display devices, and other control room equipment.
TB1 Position
Function
1
4-20 mA Output
2
MOD1-
3 MOD1+
4
MOD2-
5 MOD2+
6
Remote CAL
7 Remote
Reset
8
COM GND
9
+24 VDC Power
Table 7: TS4000H Terminal Block TB1 Pinouts
For information on the maximum recommended cable runs between the Base Unit and the
Interface Module, refer to Section 9.5.
To Connect an Analog Device to the TB1 Block
1. Fasten the analog device wire to connector TB1, position 1.
2. To make analog connections to GM display devices, refer to the following table.
From
To
TS4000H Base Unit
TA502A
TB1-1 4-20 mA Output
Rear Pin 26d or 26z
Table 8: Connection to GM Display Device 4-20 mA Connections
NOTE:
To make output signal connections to display devices, refer to the specific manual for
that device. If the 4-20 mA signal is not used, the signal wire must be connected to
Ground (Terminal TB1-8).