TS4000H
63
Byte
Function
Bit Position
Access
High
Not Used
15 MSB
Read
Not Used
14
Read
Not Used
13
Read
Not Used
12
Read
Not Used
11
Read
Not Used
10
Read
Latching / Non-Latching
9
Read / Write
Energized /
De-Energized
8
Read / Write
Low
Set point
7-0
Read / Write
Table 29: Warning Relay Settings
5.9.12 MOD1 Address (0x000F)
A read command returns the current address for MOD1. A write command changes the
address to the requested value. Valid addresses are 1-247 decimal.
Factory
default is
1
.
EXCEPTION:
If the address is not in range an Illegal Data Value (03) is returned.
5.9.13 MOD1 Baud Rate (0x0010)
A read command returns the current baud rate for MOD1. A write command changes the baud
rate to the requested values. Valid settings are shown in Table 30.
Factory default is 9600
baud.
Baud Rate
Value
Access
2400
0
Read / Write
4800
1
Read / Write
9600
2
Read / Write
19200
3
Read / Write
Table 30: MOD1 Baud Rate
EXCEPTION:
If the baud rate is not in range, an Illegal Data Value (03) is returned.
5.9.14 MOD1 Data Format (0x0011)
A read command returns the current data format for MOD1. Write command changes the data
format to the requested values. Valid settings are shown in Table 31.
Default format is 8-N-1
.
Data Bits
Parity
Stop
Format
Value
Access
8
None
1
8-N-1
0
Read / Write
8
Even
1
8-E-1
1
Read / Write
8
Odd
1
8-O-1
2
Read / Write
8
None
2
8-N-2
3
Read / Write
Table 31: Selectable Data Formats