TS4000H
37
Latching
(default)
De-energized
(default)
60% FS set point (default)
95% of FS (maximum)
Warn relay set point (minimum)
The default Alarm Relay settings for O
2
are:
17.0% by volume (default)
Warn relay set point (maximum)
60% FS (minimum)
To Adjust the Alarm Relay Settings for All Sensors Except O
2
1. Apply and hold the magnet on the GM logo on the Base Unit cover. Wait until “
SE
”
displays and then remove the magnet. This action places the unit into Setup Mode.
2. After a few seconds “
Hi
” displays. Apply and remove the magnet to change the Alarm
Relay settings.
3. First, the Energized / De-Energized state of the relay displays by either “
En
”
or “
dE
”
being displayed, respectively. Apply the magnet until the desired state is displayed, and
remove to select the desired state.
4. After a few seconds the Latching / Non-Latching state of the relay displays by either
“
LA
”
or “
nL
” being displayed, respectively. Apply the magnet until the desired state is
displayed, and remove to select the desired state.
5. After a few seconds, the current Alarm Relay set point displays. Apply and hold the
magnet to increment the set point by 1%.
6. Remove the magnet for three seconds to select the currently displayed set point. To
save the setting, apply and remove the magnet when “
Fi
” displays.
7. To exit the Setup Menu, apply and remove the magnet when “
Fi
” displays again and
return to normal operation.
NOTE:
The Alarm Relay set point cannot be set lower than the Warning Relay set point.