Technical data: inputs as seen from the IO-Link
Bit
Function
Signal
Solenoid valve Y1
activated
0 = solenoid valve
inactive
DI1
PV Y2 on
1 = solenoid valve
activated
Solenoid valve Y2
activated
0 = solenoid valve
inactive
DI2
PV Y3 on
1 = solenoid valve
activated
Solenoid valve Y3
activated
0 = solenoid valve
inactive
DI3
Error on
1= error active
Error active
0 = error inactive
DI4
Y7
not assigned
DI5
Y6
not assigned
DI6
Y5
not assigned
DI7
SUP
1= setup active
Setup active
0= setup inactive
DIW X +2
Actual valve
position
0 … 1023 (10Bit)
Valve position
0 … 78mm
* Assignment for colour variant green, see Section 6.5.2, Page 53.
Technical data: outputs as seen from the IO-Link
Bit
Function
Signal
DOB X
DO0
PV Y1
Activation of solenoid
valve Y1
1 = solenoid valve
activated
0 = solenoid valve not
activated
DO1
PV Y2
Activation of solenoid
valve Y2
1 = solenoid valve
activated
0 = solenoid valve not
activated
Technical data
IO-Link specifications
430BAL010699EN_6