EN-17
Unit indication LEDs (LED panel dedicated)
Hz
・
A
・
%
Indicates the unit of the parameter value shown on the display.
Minus polarity indication LED (LED panel dedicated)
——
Lights when the number on the display is a minus number.
Operation keys
Starts the drive in the forward direction. (in Local Mode only)
Starts the drive in the reverse direction. (in Local Mode only)
Stops the drive. The motor will either coast to a stop or ramp down to a stop as
selected on C00-1.
Held down for 2
sec.
When this key is held down for two seconds or longer during operation, the motor
will coast to stop regardless of Local Mode or Remote Mode.
+
STOP
LCL
SET
Changes control Modes from Local to Remote, or vice-versa. When the drive is in
Local Mode, "LCL" LED is on.
The drive is default set so that a Local/Remote selection is disabled while the drive is
running. Even while the drive is at a stop, this selection cannot be made if operating
commands such as RUN, JOG, etc., are being received at the terminal. This lock can
be released with Parameter C09-2.
+
STOP
RS
MO
Resets a fault, putting out FLT LED.
Parameter operation keys
・
Parameter operation knob
RST
MOD
Changes the block No. mode displayed on the indicator in the following order each
time the key is pressed:
Monitor
→
Parameter A
→
Parameter B
→
Parameter C
→
Utility Mode U.
LCL
SET
Fixes Parameter number or set its values.
Param.
Select
When main & sub-No. selection method (C11-7=2) is selected for
parameter setting method, moves from sub-No. selection to main
No. selection.
Valve change Moves the digit to increment or decrement.
Parameter increase/decrease key, parameter increase/decrease knob
or
Increases the parameter No. or parameter setting value.
or
Decreases the parameter No. or parameter setting value.
or
+
When the parameter is being set with the sub-No. selection method
(C11-7=1), increases the parameter's main No.
+
or
When the parameter is being set with the sub-No. selection method
(C11-7=1), decreases the parameter's main No.
Operations dedicated for LED panel
Held down
Increases the parameter No. or setting value at a fast speed.
Held down
Decreases the parameter No. or setting value at a fast speed.