EN-15
1) Control terminal TB1,TB2
2) Dip switches DS1
No. OFF ON
Signal
1 OPEN
120
Ω
Standard serial terminator changeover
2
V1
I1
AI1 voltage, current changeover
3
V2
I2
AI2 voltage, current changeover
4
PS03
PULSE Sequence output, pulse train output changeover
All switches are
set to OFF as the
default.
3) EL-BIT W1,W2,W3,W4
No.
1
2
Signal
W1 SINK
SOURCE PSI1
~
6 sink
,
source changeovers
W2 SINK
SOURCE PSI7 sink
,
source changeover
W3 voltage
current
AO1
voltage, current changeover
W4 voltage
current
AO2
voltage, current changeover
All EL-BITs are
set to 1 as the
default.
4) Standard serial or Modbus transmission
CN2 (Connector type: 4-pole modular, Hirose Electric TM3P-44P or equivalent)
Terminal
No.
Signal
1 DATA+
2 DATA-
3 0VOP
4 5VOP
5) Standard serial or Modbus transmission TB3
Terminal
No.
Symbol Signal
1 D+ DATA+
2 D- DATA-
3 SG 0VOP
Wire peeling size
5mm
・
The terminal block is laid out in two rows.
・
Terminal screw size is M3.
・
A signal level is based RS-485. The terminus resistance (120
Ω
) can set up on/off in DS1-1.
((DS1-1=120
Ω
): Connected, (DS1-1=OPEN): Not connected)
・
The direction of a signal is based on VAT300.
・
5VOP and 0VOP
are not designed to supply power to any external devices.
・
CN2 and TB3 DATA+, DATA- and 0VOP are connected in the PCB.
・
The terminal size is M2.
・
The applicable wire size is AWG26 to AWG16.
7.7mm
5mm
6.6mm
Outline drawing of connector
4
3
2
1
Содержание VAT300 Series
Страница 10: ...EN 8 h X075K0 X090K0 i X110K0 X132K0 j X160K0 X200K0 Fig 2 3 b cont Terminal block wiring ...
Страница 110: ...FR 8 h X075K0 X090K0 i X110K0 X132K0 j X160K0 X200K0 Fig 2 3 b cont Repérage des bornes ...
Страница 143: ...IT 8 h X075K0 X090K0 i X110K0 X132K0 j X160K0 X200K0 Fig 2 3 b Collegamenti alla morsettiera di potenza ...