Illustration 2-29: Fluoro UPS UL Layout (Optional)
The left, right or back side of the UPS cabinet can be positioned against the wall.
The front side of the UPS cabinet must be accessible for maintenance operation.
In front of the cabinet, the clear width of the service area to insure electrical safety shall be at
least 0.9 m. In cases where 2 cabinets are installed face to face (both sides of the access way),
the clear width shall be at least 1.2 m.
Recommended minimum clearance between ceiling and top of the UPS should be 400 mm (16”)
for proper cooling air exhaust.
Optima IGS 320, Optima IGS 330 Pre-Installation Manual
Direction 5537562-1-1EN, Revision 3
74