C-4
F35 MULTIPLE FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
COMMAND LINE INTERFACE
APPENDIX C: COMMAND LINE INTERFACE
C
SetupCLI <Application> compare -f <File1> -r <File2> -o <OutputFile> [-s]
Compare settings files <File1> and <File2>, and save output to <OutputFile>.
Example: SetupCLI URPC compare -f may.urs -r september.urs -o compared.txt
Batch file example that retrieves a settings file, compares it with an existing settings file, and opens the resulting
comparison file:
SetupCLI URPC start
SetupCLI URPC getsettings -d demoDevice -f devicefile.urs
SetupCLI URPC compare -f existingfile.urs -r devicefile.urs -o output.txt
The output is similar to the following:
Comparing settings file aaa.urs : C:\Users\Public\Public Documents\GE Power Management\URPC\Data\ with bbb.urs
: C:\Users\Public\Public Documents\GE Power Management\URPC\Data\
# Setting Name (Group,Module,Item) Value
1 + Default Message Timeout (1,1,1) = 299 s
2 - Default Message Timeout (1,1,1) = 300 s
3 + Flash Message Time (1,1,1) = 0.9 s
4 - Flash Message Time (1,1,1) = 1.0 s
SetupCLI <Application> inservice -d <device> [-n] [-s]
Put the device in service. Include option -n to take the device out of service.
Example: SetupCLI URPC inservice -d C30
SetupCLI <Application> reboot -d <device> [-s]
Reboot the relay <device>. This is necessary after changing IEC 61850 settings and aggregator source settings.
Example: SetupCLI URPC reboot -d "C30_Instanbul"
SetupCLI <Application> adddevice -I <IP Address> -S <Slave Address> -P <Modbus Port>
Connect to a device using its IP address, slave address, and Modbus port. Show the device in the EnerVista interface
under the SetupCLI Site as DEV@SETUP_CLI.
EnerVista UR Setup 7.30 or higher supports this command.
Figure C-2: Device added using IP address
The device is named as DEV@SETUP_CLI, which is used as the device name required by the <device> parameter of other
SetupCLI commands.
Содержание F35
Страница 12: ...1 4 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 562: ...6 30 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 576: ...7 14 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 650: ...A 38 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 658: ...C 6 F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 666: ...iv F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 682: ...xvi F35 MULTIPLE FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...