104
Advent Commercial Fire System
User Zone Test Complete
7
607
User Zone Test Incomplete
8
607
User Zone Test Trip
9
611
Installer Zone Test Started
10
607
Installer Zone Test Ended
11
607
Installer Zone Test Complete 12
607
Installer Zone Test
Incomplete
13
607
Installer Zone Test Trip
14
611
Fire Drill
15
604
System Trouble
(General Types 15–System Trouble, 16–System Trouble
Restoral)
Receiver Failure
0
355
Antenna Tamper
1
355
Main Low Battery
2
302
SnapCard Low Battery
3
302
Module Low Battery
4
338
Main AC Power Failure
5
301
Snap Card AC Power Failure 6
301
Module AC Power Failure
7
342
Auxiliary Power Failure
8
330
Shutdown
9
308
Bus Low Power Mode
10
330
Phone Line #1 Failure (will
be reported to phone 2)
11
351
Phone Line #2 Failure (will
be reported to phone 1)
12
352
Remote Phone Tamper
13
413
Watchdog Reset
14
305
RAM Failure
15
303
Flash Error
16
304
Printer Trouble
17
336
History Buffer Full
18
623
History Buffer Overflow
19
624
Report Buffer Overflow
20
624
Bus Device Failure
21
333
Failure to Communicate
22
354
Long Range Radio Trouble
23
353
Module Tamper
24
341
Unenrolled Module
25
333
Audio Amplifier Trouble
26
320
33
Table B.8 Contact ID Codes (Continued)
Description
S
p
e
c
ific
Ty
p
e
Cont
a
c
t I
D
Co
de
A
s
soc
iate
d
Zo
ne T
y
pe
Analog Module Trouble
27
333
Cell Module Trouble
28
333
Buddy #1 Failure
29
334
84, 85
Buddy #2 Failure
30
334
84, 85
Buddy #3 Failure
31
334
84, 85
Buddy #4 Failure
32
334
84, 85
SnapCard Trouble
33
333
Analog Loop Short
34
332
Analog Loop Break
35
331
Analog Head at Address 0
36
333
Unenrolled Analog Head
37
333
Duplicate Analog Head
38
333
Analog Loop Initializing
39
333
Microphone Switch Trouble
40
333
Microphone Trouble
41
333
Microphone Audio Trouble
42
333
JTech Module Trouble
43
333
Voice Siren Tamper
44
320
33
Microburst Transmit Fault
45
353
Microburst Disabled
46
353
Microburst Module Failure
47
353
Microburst not is service
48
353
Automation Module
Supervisory
49
353
System Configuration Change
(General Type 17–System Configuration Change)
Program Mode Entry
0
627
Program Mode Exit No
Change
1
628
Program Mode Exit With
Change
2
306
Download Started
3
412
Download Ended No Change 4
416
Download Ended With
Change
5
412
Download Error
6
413
Download Denied
7
413
Date/Time Changed
8
625
Expansion Module Added
9
531
Expansion Module Deleted
10
532
Speech Tokens Changed
11
306
Program Code Changed
12
306
Table B.8 Contact ID Codes (Continued)
Description
S
p
e
c
ific
Ty
p
e
Cont
a
c
t I
D
Co
de
A
s
soc
iate
d
Zo
ne T
y
pe