3
Advent Commercial Fire System
Household Fire Warning System Units (UL 985)
Basic system, plus:
Hardwire Smoke Detector (Compatibility Identifier
60-562, 20 per loop maximum):
System Sensor models 2100S, 2100TS, 2100D,
2100TD, 2400, or 2400TH added (learned) into Zone
Type 80.
Sentrol models 429AT, 521B, or 521BXT added
(learned) into Zone Type 80.
The basic system may also include:
SuperBus 2000 RF Transceiver (60-821) for use with
listed wireless signaling devices.
Wireless Smoke Sensor (60-506-319.5 or 60-848-02-95)
added (learned into Zone Type 80.
SuperBus 2000 Printer Automation Module
(60-783) for use with a listed printer.
SuperBus 2000 Dual Phone Line Module (60-768) for
expansion to primary and secondary phone line reporting.
24V Smoke Loop SnapCard (60-767).
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 985 listed systems:
Household Burglar-Alarm System Units (UL 1023)
Basic system plus:
Hardwire Magnetic Contact (13-068 or 13-071)
The basic system may also include:
SuperBus 2000 RF Transceiver (60-821) for use with
listed wireless signaling devices.
Wireless Learn Mode Door/Window Sensor (60-362)
SuperBus 2000 Printer or Automation Module
(60-783) for use with a listed printer.
SuperBus 2000 Dual Phone Line Module (60-768) for
expansion to primary and secondary phone line reporting.
System Setup and Programming
The system Feature Numbers shall be set as follows in
UL 1023 listed systems:
Table 4. UL 985 Listed System Settings
Feature
No.
Feature
Required Setting
xx002
Siren Time Out
4 min. minimum
xx003
Standard Entry Delay
45 sec. maximum
xx004
Exit Delay
60 sec. maximum
yy004
Communication Format
0 Contact ID
xx085
Enable Police Panic Keys
1-On
xx086
Enable Auxiliary/Medical
Panic Keys
1-On
xx087
Enable Fire Panic Keys
1-On
xx088
Report Partition/Area Events
to Central Station
1-On
xx092
Enable Auto Force Arming
0-Off
xx097
Exterior Arming Verification
0-Off
xx102
One-Time Reset Enabled
0-Off
xx108
Enable Daily Reporting of
Partition Trouble
1-On
17036
AC Stable Time
90 sec. maximum
17041
Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049
RF Supervisory Time A
4 hours
17069
No Phone Line Attached
0-Off
17072
Enable RF Jam Detect
1-On
17073
Battery Test Interval
1-4 hours
17076
Commercial or Residential
Installation
0-Off Residential
17078
Detect Receiver Failure
1-On
17079
Alarm Messages Play at High
Volume
1-On High
17096
Report System Events
1-On
47004
Zone Attributes (edit zones)
N/A
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 5. UL 1023 Listed System Settings
Feature No.
Feature
Required Setting
xx002
Siren Time Out
6 min. minimum
xx003
Standard Entry Delay
45 sec. maximum
xx004
Exit Delay
60 sec. maximum
yy004
Communication Format
0 Contact ID
xx088
Report Partition/Area Events
to Central Station
1-On
xx092
Enable Auto Force Arming
0-Off
xx097
Exterior Arming Verification 0-Off
xx102
One-Time Reset Enabled
0-Off
xx108
Enable Daily Reporting of
Partition Trouble
1-On
17036
AC Stable Time
90 sec. maximum
17041
Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049
RF Supervisory Time A
4 hours
17069
No Phone Line Attached
0-Off
17072
Enable RF Jam Detect
1-On
17073
Battery Test Interval
1-4 hours
17076
Commercial or Residential
Installation
0-Off Residential
17078
Detect Receiver Failure
1-On
17079
Alarm Messages Play at High
Volume
1-On High
17096
Report System Events
1-On
Table 4. UL 985 Listed System Settings (Continued)
Feature
No.
Feature
Required Setting