Advent Commercial Fire System
False Alarm
Alarm is being sent by mistake.
Enter the access code immediately to cancel the alarm. This command aborts the alarm report if
done within 5 seconds (alarm report delay time [xx013]) after alarm activation (Dialer Abort
feature must be on). The system will indicate
Report Canceled
and the report will not be sent to
the monitoring station.
Note
Some alarms such as Fire alarms will not be aborted.
Hardwire Alphanumeric Touchpad
Touchpad displays
Touchpad Not Enrolled
and does not respond to buttons.
Enter panel programming mode by entering 8 + 0 and the install code at a working touchpad or
from a telephone.
Enter item number 48001 and enroll the new touchpad into panel memory.
Touchpad displays
**********
and does not respond to button presses.
Check for SuperBus miswiring.
Hardwire Alphanumeric Touchpad (continued)
Touchpad appears “dead” (no display or response to buttons).
1. Check that the wiring connector is plugged into the back of the touchpad and into the panel
bus connector.
2. Check SuperBus wiring for opens or shorts.
3. Check panel power.
Hardwire Inputs
No inputs detected.
1. Check panel programming of all general purpose inputs/outputs.
2. Check all input device wiring and connections.
One input is never detected.
1. Check panel programming of general purpose input/output.
2. Check input device operation.
3. Check input device wiring and connections.
Wrong input is detected.
1. Check panel input programming for input.
2. Check input device wiring and connections.
Hardwire Outputs
No outputs activate.
1. Check panel/module programming.
2. Check output wiring and connections.
3. Check panel/module power (green LEDs on).
4. If used, check the optional external supply powering the output devices.
One output never activates.
1. Check panel/module programming for that output.
2. Check output wiring and connections.
3. Check that the output programmed trigger event actually occurs.
4. Output relay may have failed or been overloaded. Reprogram to use a different (unused) out-
put or replace the module.
Wrong output activates.
1. Check panel output programming.
2. Check output device wiring and connections.
Feature
Problem
Solution