Advent Commercial Fire System
System Settings
Note
Date, time, and day settings affect all partitions/areas.
First Disarm Silences Fire Alarm and Second Disarm
Cancels the Alarm
17084
(Alarms)
(Default = on) When set to on, the first code entry will silence a
fire alarm and the second code entry will cancel the alarm. If off,
the first code entry will silence
and
cancel the alarm.
To turn First Disarm Silences Fire Alarm and
Second Disarm Cancels the Alarm On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Unsilence Alarm after Silencing Period
17126
(Alarms)
(Default = off) Choose whether or not to enable unsilencing of
alarm after silencing period expires. If on, a silenced fire alarm
will resound.
Note
The silencing period can be set using the
Time Fire Alarm
is Silenced
setting (17111) below.
To turn Unsilence Alarm After Silencing Period
On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Time Fire Alarm is Silenced
17111
(Alarms)
(Default = 30 seconds) Specify the amount of time (in seconds),
for which sirens are silenced during a fire alarm (after a user
enters a valid access code).
Note
The alarm will not unsilence if
Unsilence Alarm after
Silencing Period
setting (17126) is set to off.
To set Time Fire Alarm is Silenced:
Once the item number has been entered, specify the silence time
(15–999). Press
ƒ
to apply the new setting.
Annunciate Earliest Fire Alarm not the Most Recent
17128
(Alarms)
(Default = off) If on, the panel will annunciate the earliest active
fire alarm instead of the most recent, during a multiple fire alarm
situation.
Note
This option is intended for panels installed in Canada.
To turn Annunciate Earliest Fire Alarm not the
most Recent On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Fire Alarm in One Partition Sounds In All Partitions
17077
(Alarms)
(Default = on) Enable if you want a fire alarm in one partition to
sound in all partitions. If not, a fire alarm will only sound in the
partition where it occurred.
Note
This option is not available in UL-864 version.
To turn Fire Alarm in One Partition Sounds In All
Partitions On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
System Strobe Light Type
17062
(Alarms)
(Default = 1 [Amseco]) This setting allows you to choose the
strobe manufacturer synchronization type.
Strobe Light Types:
1— Amseco
2— Wheelock
3— System Sensor
4— Gentex
Note
This option can only be programmed through Advent
Downloader.
Medical Siren Cadence
Police Siren Cadence
Auxiliary Siren Cadence
17046, 17047, 17048
(Alarms)
(Defaults = Medical: alternate modulated, Police: steady,
Auxiliary: fast modulated) Set the siren cadence to the desired
sound rhythm.
Sound Rhythms:
(_ represents 0.125 second sound, ___represents 0.5 second
sound)
1— Temporal 3 ___
___
___ (repeat)
2— Modulated ___
___
___
___(repeat)
3— Alternate Modulated ___ _ _ ___ (repeat)
4— Fast _ (repeat)
5— Steady ___________ (steady on)
6— Programmable Cadence (must program through
downloader)
To set Siren Cadence:
1.
Once in program mode enter the desired item number.
2.
Enter the desired sound rhythm (1–6) and press
ƒ
.