Table B.10 LED Types and Behaviors
LED Types
LED Type Behavior
LED
Type
Description
LED Data
When the Green
LED is On
When the Yellow
LED is On
When the RED
LED is On
0
Disable all LED’s (default)
1
Zone status type 1
Zone number
Zone normal
Zone in trouble or
bypassed
Zone in alarm
2
Zone status type 2
Zone number
Zone normal
Zone open, in
trouble, or bypassed
Zone in alarm
3
Zone status type 3
Zone number
Zone normal
Zone in trouble or
bypassed
Zone open
(unrestored)
4
Programmable output status type 1 Output number
Output off
Output on
5
Programmable output status type 2 Output number
Output off
Output on
6
Arming level
Partition/Area
Partition/Area
disarmed
Partition/Area armed
7
Alarm/Trouble status
Partition/Area
Partition/Area normal Partition/Area in
trouble
Partition/Area in
alarm
8
System trouble
No system trouble
System trouble
9
Main AC trouble
Main AC on
Main AC off
10
SnapCard AC trouble
SnapCard AC on
SnapCard AC off
11
Module AC trouble
Module AC on
Module AC off
12
Auxiliary power trouble
Auxiliary power OK
Auxiliary power
trouble
13
Main battery trouble
Main battery(s) OK
Main battery(s) low
14
SnapCard battery trouble
SnapCard battery(s)
OK
SnapCard battery(s)
low
15
Module battery trouble
Module battery OK
Module battery(s)
low.
Note:
If no LEDs are on, either the group is not programmed or the partition/area is not enabled.