![GE Advent Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/ge/advent/advent_installation-instructions-manual_132114053.webp)
51
Advent Commercial Fire System
4.
Set the house dial on the module to the appropriate let-
ter.
5.
Set the unit number dial from 1 to 16 for the desired
response as described in Table B.6 on page 97.
Adding Lights/Devices to Program
Memory
To add lights or devices to program memory:
1.
Press
7
. The display shows
FEATURES MENU
.
2.
Enter
3
and the display shows
LEARN LIGHTS AND
DEVICES.
3.
Press
1
to add a light. The panel displays
ENTER A
LIGHT NUMBER THEN PRESS #.
Press
4
to add a device. The panel displays
ENTER A
DEVICE NUMBER THEN PRESS #.
4.
Enter the desired light or device number (1–40) and
press
ƒ
. The display shows
LIGHT/DEVICE nn
ADDED.
5.
To add another light or device, enter the desired light or
device number and press
ƒ
.
6.
To exit press
‚
+
‚
.
To delete lights or devices from program memory:
1.
Press
7
. The display shows
FEATURES MENU
.
2.
Enter
3
and the display shows
LEARN LIGHTS AND
DEVICES.
3.
Press
2
to delete a light. The panel displays
ENTER A
LIGHT NUMBER THEN PRESS #.
Press
5
to delete a device. The panel displays
ENTER
A DEVICE NUMBER THEN PRESS #.
4.
Enter the desired light or device number (1–40) and
press
ƒ
. The display shows
LIGHT/DEVICE nn
DELETED.
5.
To delete another light or device enter the desired light
or device number and press
ƒ
.
6.
To exit press
‚
+
‚
.
Testing the System
Note
Before testing, it is recommended that you have covers on
all modules (mounted outside the cabinet) and the panel
cabinet door closed. The
testing
environment should
match the system
working
environment.
This section describes how to perform the following test
procedures:
Basic System Commands
Testing Panel Backup Battery(s)
Testing Hardwired Zone Inputs
Testing Wireless Sensors
Testing Outputs
Testing Optional Lights and Devices
(X10 Modules)
Testing Phone Communication
Testing Central Station Communication
Adjusting Touchpad Contrast
You should test the system after installing, servicing, and
adding or removing devices from the system.
Refer “Troubleshooting” on page 55 if correct test results
are not achieved.
Basic System Commands
Table 14 describes basic touchpad operating commands.
For complete details on system operation, including user
programming, refer to the system
User Guide
.
Testing Panel Backup Battery(s)
The panel can both automatically and manually place a test
load on the panel backup battery(s) and measure the voltage
output.
Note
A newly installed battery may require up to eight hours
under panel power before an accurate charge indication.
To manually test the panel backup battery(s):
1.
Press
8
. The display shows
SYSTEM MENU
.
2.
Press
8
again to test the battery(s) and display the
result. The display will show the battery voltage as
BATTERY TEST: 13.8 V
(or similar)
TO QUIT PRESS
*
.
3.
Press
‚
to quit. The system will automatically quit the
battery test after 15 minutes.
Testing Hardwire and Wireless Zones/
Sensors
It is recommended that you test all hardwired zones and
sensors after all programming is completed and whenever a
zone/sensor-related problem occurs.
Note
While the zone test is a valuable installation and service
tool, it only tests zone operation for the current conditions.
You should perform a zone test after any change in envi-
ronment, equipment, or programming.
Table 14. Basic Touchpad Operating Commands
Command
System Response
1 + 9
Indicates current system status
1 + 1 + CODE
Disarms system to OFF
1 + 2 + CODE
Arms system to PERIMETER
1 + 3 + CODE
Arms system to FULL
8 + 9 + CODE
Manually reset smoke sensors
1 + 0
Check alarm history
7 + 5
Check event history buffer
7 + 7 + CODE + Area
Area jump
8 + 8
Initiates a battery test
8 + 1 + CODE
Initiates a zone test
0 + 1 + CODE
Initiates a phone test
8 + 7 + CODE
Initiates a fire test