Advent Commercial Fire System
UL Listed Speaker
Use a UL listed 4-8 ohm, 30 watt speaker for siren applica-
tions such as status and a voice alarm annunciation speaker
for voice. When wiring multiple speakers, the total
impedange must be between 4 and 8 ohms. Connect the
speaker(s) to the panel as shown in Figure 16. For mounting
instructions please refer to the
Installation Instructions
included with the speaker.
Figure 16.Connecting 15- and 30-Watt Interior
Speakers
Connecting Sirens
Connect a exterior siren to the panel as shown in Figure 17.
Note
This siren is for supplementary use only.
Figure 17.Connecting the Hardwire Exterior siren to
the panel.
Connecting Commercial Fire Devices
For information on connecting commercial fire devices
please see Appendix C on page 109.
Installing an RJ-31X Phone Jack (13-081)
Use the following guidelines when installing an RJ-31X
phone jack for system control by phone and central station
monitoring.
Locate the RJ-31X jack (CA-38A in Canada) no further
than five feet from the panel.
The panel must be connected to a standard analog (loop-
start) phone line, that provides around 48 volts DC (on-
hook or idle).
Note
The panel cannot be used on a digital or PBX phone line.
These systems are designed for digital type devices only,
operating anywhere from 5 volts DC and up. The panel
uses an analog modem and does not have a digital con-
verter, adapter, or interface to operate through such sys-
tems.
For full line seizure, install an RJ-31X phone jack on the
premises phone line so the panel is ahead of all phones
and other devices on the line. This allows the panel to take
control of the phone line when an alarm occurs, even if the
phone is in use or off-hook.
If an analog line is not available, contact your customer’s
telecommunications specialist and tell him/her you need
an analog line off the phone switch (PBX mainframe) or a
1FB (standard business line).
Note
Connecting the panel to an analog line off the phone
switch places the panel
ahead
of the phone system, pre-
venting panel access from phones on the premises. How-
ever, the panel can still be accessed from off-site phones.
To connect a phone line to the panel using an
RJ-31X/CA-38A jack:
1.
Run a 4-conductor cable from the TELCO protector
block to the jack location (see Figure 18).
2.
Connect one end of the cable to the jack.
3.
At the TELCO protector block, remove the premises
phone lines (lines from phone jacks on premises) from
the block and splice them to the black and white (or
yellow) wires of the 4-conductor cable.
4.
Connect the green and red wires from the 4-conductor
cable to the A (+) and B (-) posts on the block (see Fig-
ure 18).
5.
If desired, add phone jack tamper by splicing the black
and yellow phone jack wires to the panel terminals and
adding a 2.0K ohm EOL resistor between the blue and
orange phone jack terminals as shown in Figure 18.
6.
Check the phones on the premises for dial tone and the
ability to dial out and make phone calls. If phones do
not work correctly, check all wiring and correct where
necessary. Proceed to “Troubleshooting” on page 55 if
problems persist.
P a n e l T e r m i n a l S t r i p s
V o i c e
S i r e n
V o i c e
S i r e n
T w o L i s t e d 8 O H M S p e a k e r s
i n P a r a l l e l ( 4 O H M S )
O R
L i s t e d 8 O H M S p e a k e r
( 3 0 W A T T )
2 . 0 K O H M
E O L R E S I S T O R
4 9 - 4 6 7
( L O C A T E A T
L A S T D E V I C E )
2 2 0 M F , 3 5 V
C a p a c i t o r
( N o n - P o l a r i z e d )
1 7 - 1 0 1
( L o c a t e d a t D e v i c e )
2 . 0 K O H M
E O L R E S I S T O R
4 9 - 4 6 7
( L O C A T E A T
L A S T D E V I C E )
9
1 0
9
1 0
P a n e l T e r m i n a l S t r i p s
V o i c e
S i r e n
V o i c e
S i r e n
8543139B.DSF
4
5
6
7
8
INT.
BELL
RTN
+12
VDC
OUT
HARDWIRE
EXTERIOR SIREN
RED
BLACK
PANEL TERMINALS
EXT. SIREN/HORN
IN
FOR SUPPLEMENTARY USE ONLY