8-20
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
THE IEC 61850 CONFIGURATOR
CHAPTER 8: IEC 61850
Note that the Goose control block can also be deleted by right clicking on the
configured existing report.
•
Save button and Cancel button: Click the Save button to save all configured settings.
Click the Cancel button to discard the modifications just made to the configuration.
Add GOOSE Transmission Control Block
1.
Click on the “Add GOOSE Control Block” button.
2.
The Tx GOOSE control block is added under GEDevice>869 tree node with a default
Control block name.
Figure 8-15: Goose TX Control Blocks
Goose Tx Properties
The properties section can be viewed on selecting any configured GOOSE block available
under GEDevice >869.
Figure 8-16: Goose TX Properties Screen
Parameters for Goose TX
•
GOOSE ID: The range of the setting is 129-characters
•
Time to live (ms): The range of the setting is 1000 to 60000 in steps of 1000
•
Multicast MAC: The standard MAC address limit. Make sure to configure the MAC with
the least significant bit in the most significant byte, set to 1.
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...