4-8
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
DNP IMPLEMENTATION
CHAPTER 4: DNP 3
DNP implementation
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER CODES (HEX) FUNCTION CODES
(DEC)
QUALIFIER CODES
(HEX)
1
0
Binary Input
(Variation 0 is used
to request default
variation)
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
Binary Input
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2
Binary Input with
Status
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2
0
Binary Input Change
(Variation 0 is used
to request default
variation)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
---
---
1
Binary Input Change
without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
2
Binary Input Change
with Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
3
Binary Input Change
with Relative Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
---
---
10
0
Binary Output Status
(Variation 0 is used
to request default
variation)
1 (read)
00, 01(start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
2
Binary Output Status 1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
12
1
Control Relay Output
Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
echo of request
20
0
Binary Counter
(Variation 0 is used
to request default
variation)
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
32-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2
16-Bit Binary
Counter
1 (read)
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...