![GE 869 Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/ge/869/869_communications-manual_4102486076.webp)
8-18
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
THE IEC 61850 CONFIGURATOR
CHAPTER 8: IEC 61850
Goose Transmission
The 869 relay has an IEC 61850 server and supports the GOOSE message scheme. A
maximum of three GOOSE control blocks can be added. The GOOSE Configuration has two
sections:
•
Transmission
•
Reception
GOOSE transmission configuration is described in this section.
Figure 8-13: Goose Transmission Screen
The GOOSE Transmission window has two screens.
•
GOOSE Tx control blocks: The user can add the required GOOSE control block.
–
Control Block Name:
The first character in the value of this attribute must be a
letter (upper or lower case). The rest of the characters must be a number, a letter
(upper or lower case) or a “_”. The maximum number of characters allowed is 32.
–
Description:
The maximum number of characters allowed is 32.
–
GOOSE ID:
The maximum number of characters allowed is 129.
–
Ethertype App ID:
All characters must be numerical. The maximum number of
characters allowed is 4. IEC61850 Configurator allows characters limited to 0 to
9, A to F and it saves in the CID file the hexadecimal value (max FFFF).
3
1
4
2
2
4
1
3
4
Buffered Report
Unbuffered Report
Total Reports
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...