CHAPTER 8: IEC 61850
THE IEC 61850 CONFIGURATOR
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
8-19
–
Multicast MAC:
6 pairs of letters (from A to F, upper case or lower case) or
numbers separated by colons.
–
VLAN priority:
A number from 0 to 7.
–
VLAN identifier:
The maximum number of characters allowed is 3. IEC61850
Configurator allows characters limited to 0 to 9, A to F and it saves in the CID file
the hexadecimal value (max FFF).
•
Dataset sources: Each GOOSE control block can be appended with dataset items in
this screen using a drag and drop operation.
–
DataSet Name
: The first character in the value of this attribute must be a letter
(upper or lower case). The rest of the characters must be a number, a letter (upper
or lower case) or a “_”. The maximum number of characters allowed is 32.
–
Description:
The maximum number of characters allowed is 32.
Figure 8-14: Goose TX Control Blocks and DataSet Sources Screen
The following buttons are available in the Goose Transmission window:
•
“Add GOOSE Control Block” button and “Remove GOOSE Control Block” button: Both
buttons are in the lower side of the screen.
•
Note that a GOOSE Control block can also be added by right clicking on “869 ” which is
under the GEDevice “tree”.
The “Remove Goose Control Block” button deletes a configured existing Goose control
block.
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...