11-22
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 11: MODBUS MEMORY MAP
33102
0x0C1D
Arcing Current Phase B
0
4294967295 1
kA2-cyc
F12
0
1
33104
0x0C1F
Arcing Current Phase C
0
4294967295 1
kA2-cyc
F12
0
1
33106
0x0C21
Total Arcing Current
0
4294967295 1
kA2-cyc
F12
0
1
Digital Counter Status 1
33140
0x0C43
Counter 1 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33142
0x0C45
Counter 1 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33144
0x0C47
Date/Time - Frozen
0
0xFFFFFFFF
1
F50
0
1
33146
0x0C49
Counter 1 us - Frozen
0
999999
1
us
F51
0
1
Digital Counter Status 2
33152
0x0C4F
Counter 2 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33154
0x0C51
Counter 2 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33156
0x0C53
Date/Time - Frozen
0
0xFFFFFFFF
1
F50
0
1
33158
0x0C55
Counter 2 us - Frozen
0
999999
1
us
F51
0
1
Digital Counter Status 3
33164
0x0C5B
Counter 3 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33166
0x0C5D
Counter 3 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33168
0x0C5F
Date/Time - Frozen
0
0xFFFFFFFF
1
F50
0
1
33170
0x0C61
Counter 3 us - Frozen
0
999999
1
us
F51
0
1
Digital Counter Status 4
33176
0x0C67
Counter 4 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33178
0x0C69
Counter 4 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33180
0x0C6B
Date/Time - Frozen
0
0xFFFFFFFF
1
F50
0
1
33182
0x0C6D
Counter 4 us - Frozen
0
999999
1
us
F51
0
1
Digital Counter Status 5
33188
0x0C73
Counter 5 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33190
0x0C75
Counter 5 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33192
0x0C77
Date/Time - Frozen
0
0xFFFFFFFF
1
F50
0
1
33194
0x0C79
Counter 5 us - Frozen
0
999999
1
us
F51
0
1
Digital Counter Status 6
33200
0x0C7F
Counter 6 Accumulated
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
33202
0x0C81
Counter 6 Frozen
-2147483648 2147483647 1
User-
Programma
ble Units
F30
0
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...