4-10
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
DNP IMPLEMENTATION
CHAPTER 4: DNP 3
30
0
Analog Input
(Variation 0 is used
to request default
variation)
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
32-Bit Analog Input 1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2
16-Bit Analog Input 1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
3
32-Bit Analog Input
without Flag
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
4
16-Bit Analog Input
without Flag
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
5
short floating point
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
32
0
Analog Change
Event (Variation 0 is
used to request
default variation)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
---
---
1
32-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
2
16-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
3
32-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
4
16-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
5
short floating point
Analog Change
Event without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
7
short floating point
Analog Change
Event with Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
34
0
Analog Input
Reporting Deadband
(Variation 0 is used
to request default
variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
16-bit Analog Input
Reporting Deadband
(default - see Note 1)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2 (write)
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
---
---
2
32-bit Analog Input
Reporting Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER CODES (HEX) FUNCTION CODES
(DEC)
QUALIFIER CODES
(HEX)
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...