11-58
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
CHAPTER 11: MODBUS MEMORY MAP
50386
0x2891
Name
0
65535
1
F60_26 RTD 6
26
50399
0x289E
Type
0
3
1
FC120
0
1
50400
0x289F
Application
0
4
1
FC121
0
1
50401
0x28A0
Voting
0
12
1
FC122
0
1
50402
0x28A1
Trip Temperature
1
250
1
°C
F20C
155
1
50403
0x28A2
Trip Pickup Delay
0
600
1
s
F0
2
1
50404
0x28A3
Trip Dropout Delay
0
600
1
s
F0
0
1
50405
0x28A4
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50407
0x28A6
Alarm Function
0
3
1
FC100E 0
1
50408
0x28A7
Alarm Temperature
1
250
1
°C
F20C
130
1
50409
0x28A8
Alarm Pickup Delay
0
600
1
s
F0
2
1
50410
0x28A9
Alarm Dropout Delay
0
600
1
s
F0
0
1
50411
0x28AA
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50413
0x28AC
Sensor Open
0
2
1
FC354
0
1
50414
0x28AD
Block
0
0xFFFFFFFF
1
FC142
0
1
50416
0x28AF
Events
0
1
1
FC126
1
1
50417
0x28B0
Targets
0
2
1
FC101
2
1
RTD 7 Input Setpoints
50418
0x28B1
Trip Function
0
4
1
FC100D 0
1
50419
0x28B2
Name
0
65535
1
F60_26 RTD 7
26
50432
0x28BF
Type
0
3
1
FC120
0
1
50433
0x28C0
Application
0
4
1
FC121
0
1
50434
0x28C1
Voting
0
12
1
FC122
0
1
50435
0x28C2
Trip Temperature
1
250
1
°C
F20C
155
1
50436
0x28C3
Trip Pickup Delay
0
600
1
s
F0
2
1
50437
0x28C4
Trip Dropout Delay
0
600
1
s
F0
0
1
50438
0x28C5
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
50440
0x28C7
Alarm Function
0
3
1
FC100E 0
1
50441
0x28C8
Alarm Temperature
1
250
1
°C
F20C
130
1
50442
0x28C9
Alarm Pickup Delay
0
600
1
s
F0
2
1
50443
0x28CA
Alarm Dropout Delay
0
600
1
s
F0
0
1
50444
0x28CB
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
50446
0x28CD
Sensor Open
0
2
1
FC354
0
1
50447
0x28CE
Block
0
0xFFFFFFFF
1
FC142
0
1
50449
0x28D0
Events
0
1
1
FC126
1
1
50450
0x28D1
Targets
0
2
1
FC101
2
1
RTD 8 Input Setpoints
50451
0x28D2
Trip Function
0
4
1
FC100D 0
1
50452
0x28D3
Name
0
65535
1
F60_26 RTD 8
26
50465
0x28E0
Type
0
3
1
FC120
0
1
50466
0x28E1
Application
0
4
1
FC121
0
1
50467
0x28E2
Voting
0
12
1
FC122
0
1
50468
0x28E3
Trip Temperature
1
250
1
°C
F20C
155
1
50469
0x28E4
Trip Pickup Delay
0
600
1
s
F0
2
1
50470
0x28E5
Trip Dropout Delay
0
600
1
s
F0
0
1
50471
0x28E6
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...