11-308
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES
CHAPTER 11: MODBUS MEMORY MAP
0
Modbus
1
IEC60870-5-103
2
DNP 3.0
FC210
unsigned 16 bits
RS 485 Baud Rate
0
9600 baud
1
19200 baud
2
38400 baud
3
57600 baud
4
115200 baud
FC211
unsigned 16 bits
RS 485 Parity
0
None
1
Odd
2
Even
FC212
unsigned 16 bits
ASDU Ident Type
0
3
1
9
FC217
unsigned 16 bits
Ethernet Duplicate
0
Discard
1
Accept
FC218
unsigned 16 bits
Ethernet Mode
1
Full-Duplex
FC219
unsigned 16 bits
Ethernet Port 4/5 Operation
0
Independent
1
LLA
2
PRP
FC220
unsigned 16 bits
IRIG-B Signal Type
0
None
1
DC Shift
2
Amplitude Mod.
FC226
unsigned 16 bits
WiFi Infrastructure Security
0
None
1
WPA2-PSK
FC228
unsigned 16 bits
61850 Status
0x0001
Comms NV OK
0x0002
Comms NV Done
0x0004
Comms V OK
0x0008
Comms V Done
0x0010
Main NV OK
0x0020
Main NV Done
0x0040
Main V OK
0x0080
Main V Done
0x0100
NR. Error CID
0x0200
R. Default CID
0x0400
R. Saving CID to Flash
0x0800
CID Handling Done
FC229
unsigned 16 bits
DNP Analog Input Point Scale Factor
1
/ 0.001
Code
Type
Definition
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...