CHAPTER 2: COMMUNICATION PORTS
ETHERNET PORTS
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
2-11
Figure 2-3: Topology Example
In the above figure: Topology Example, the 8 Series device is connected through the two
Ethernet ports available on the communications card.
•
Port 4 (IP address 10.1.1.2) connects to LAN 10.1.1.0/24 and to the Internet through
Router1. Router 1 has an interface on 10.1.1.0/24 and the IP address of this interface
is 10.1.1.1.
•
Port 5 (IP address 10.1.2.2) connects to LAN 10.1.2.0/24 and to EnerVista setup
program through Router 2. Router 2 has an interface on 10.1.2.0/24 and the IP
address of this interface is 10.1.2.1.
Configuration
Network addresses:
PRT54IP ADDRESS = 10.1.1.2PRT4 SUBNET IP MASK = 255.255.255.0PRT5 IP ADDRESS =
10.1.2.2PRT5 SUBNET IP MASK = 255.255.255.0
Routing Settings:
IPV4 DEFAULT ROUTE: GATEWAY ADDRESS = 10.1.1.1
STATIC NETWORK ROUTE 1:
–
RT1 DESTINATION = 10.1.3.0/24RT1 NET MASK = 255.255.255.0RT1 GATEWAY =
10.1.2.1
Behavior: One static network route was added to the destination 10.1.3.0/24, where a
laptop running EnerVista is located. This static route uses a different gateway (10.1.2.1)
than the default route. This gateway is the address of Router 2, which is “aware” of
destination 10.1.3.0 and is able to route packets coming from the 8 Series device and
destined to EnerVista.
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...