CHAPTER 11: MODBUS MEMORY MAP
MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
11-115
63148
0x5A6B
VD Accel. Intersect @
100% V
150
2000
1
x FLA
F2
500
1
63149
0x5A6C
Alarm Function
0
3
1
FC100E 0
1
63150
0x5A6D
Alarm Pickup
1000
10000
100 % TC
F2
7500
1
63151
0x5A6E
Alarm Output Relays
0
0xFFFFFFFF
1
FC198C 0
1
63153
0x5A70
Trip Output Relays
0
0xFFFFFFFF
1
FC198D 0
1
63155
0x5A72
Block
0
0xFFFFFFFF
1
FC142
0
1
63157
0x5A74
Events
0
1
1
FC126
1
1
63158
0x5A75
Targets
0
2
1
FC101
2
1
Current Unbalance
63170
0x5A81
Name
0
65535
1
F60_26 Cur Unbal
26
63183
0x5A8E
Trip Function
0
4
1
FC100D 0
1
63184
0x5A8F
Trip Pickup
40
500
1
%
F1
150
1
63185
0x5A90
Trip Pickup Delay
0
18000
1
s
F2
100
1
63186
0x5A91
Trip Dropout Delay
0
18000
1
s
F2
100
1
63187
0x5A92
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
63189
0x5A94
Alarm Function
0
3
1
FC100E 0
1
63190
0x5A95
Alarm Pickup
40
500
1
%
F1
150
1
63191
0x5A96
Alarm Pickup Delay
0
18000
1
s
F2
100
1
63192
0x5A97
Alarm Dropout Delay
0
18000
1
s
F2
100
1
63193
0x5A98
Alarm Relays
0
0xFFFFFFFF
1
FC198C 0
1
63195
0x5A9A
Block
0
0xFFFFFFFF
1
FC142
0
1
63197
0x5A9C
Events
0
1
1
FC126
1
1
63198
0x5A9D
Targets
0
2
1
FC101
1
1
Mechanical Jam
63210
0x5AA9
Name
0
65535
1
F60_26 Mech Jam
26
63223
0x5AB6
Function
0
4
1
FC100
0
1
63224
0x5AB7
Pickup
100
1000
1
x FLA
F2
200
1
63225
0x5AB8
Pickup Delay
10
18000
1
s
F2
100
1
63226
0x5AB9
Dropout Delay
0
18000
1
s
F2
100
1
63227
0x5ABA
Relays
0
0xFFFFFFFF
1
FC198
0
1
63229
0x5ABC
Block
0
0xFFFFFFFF
1
FC142
0
1
63231
0x5ABE
Events
0
1
1
FC126
1
1
63232
0x5ABF
Targets
0
2
1
FC101
2
1
Undercurrent
63250
0x5AD1
Name
0
65535
1
F60_26 Undercur
26
63263
0x5ADE
Trip Function
0
4
1
FC100D 0
1
63264
0x5ADF
Start Block Delay
0
60000
1
s
F2
50
1
63265
0x5AE0
Trip Pickup
10
95
1
x FLA
F2
70
1
63266
0x5AE1
Trip Pickup Delay
0
18000
1
s
F2
100
1
63267
0x5AE2
Trip Dropout Delay
0
18000
1
s
F2
100
1
63268
0x5AE3
Trip Relays
0
0xFFFFFFFF
1
FC198D 0
1
63270
0x5AE5
Alarm Function
0
3
1
FC100E 0
1
63271
0x5AE6
Alarm Pickup
10
95
1
x FLA
F2
70
1
63272
0x5AE7
Alarm Pickup Delay
0
18000
1
s
F2
100
1
63273
0x5AE8
Alarm Dropout Delay
0
18000
1
s
F2
100
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
Содержание 869
Страница 6: ...1 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE COMMUNICATIONS CHAPTER 1 INTRODUCTION...
Страница 18: ...2 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE ETHERNET PORTS CHAPTER 2 COMMUNICATION PORTS...
Страница 36: ...4 12 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP 3...
Страница 82: ...8 24 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 84: ...9 2 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE CHAPTER 9 FILE TRANSFER PROTOCOLS...
Страница 94: ...10 10 869 MOTOR PROTECTION SYSTEM COMMUNICATIONS GUIDE MODBUS PROTOCOL CHAPTER 10 MODBUS PROTOCOL...